Simply install the IntelliPoint RF Series into the tank and apply power …that's it! Unlike other RF or capacitance systems that require calibration via setpoint potentiometers, jumpers, magnets, or pushbuttons. The IntelliPoint RF Series reliably detects the absence or presence of material without any adjustments.
The IntelliPoint RF Series software continuously monitors the application for changes in composition, dielectric or conductivity, and maintains a repeatable trip point on the probe. Other RF and capacitance systems require calibration adjustments when the process material is changed.
Since the IntelliPoint RF Series recognizes changes in material,it is ideal for non-dedicated tanks that are used for a wide variety of products.
-
Line Powered
-
Two-Wire
-
SIL Conforming
-
Sanitary
-
Manual Set-point
-
No calibration or setpoint adjustments.
-
Ignores changes in dielectric or conductivity.
-
Automatically recognizes and ignores coatings to prevent false alarms.
-
Continuous self-test monitors circuits and sensing elements for faults.
-
Universal power supply automatically detects input power source.
Specifications for Two Wire (RNT Series) IntelliPoint
Technology: RF Admittance
Calibration: None
Modes Of Operation: High and Low Level
Repeatability: 2 mm (0.08 inch)conductive liquids.
Response Time: less than one second.
Ambient Electronic Temperature: -30 to 70 °C (-28 to 158 °F)KEMA. -40 to 70 °C (-40 to 158 °F)FM /CSA
Storage Temperature: -40 to 85 °C (-40 to 185 °F)
Self Check: AutoVerify automatically and continuously checks electronics and sensing element for faults. Manual Certify checks that the AutoVerify circuits are functioning.
Time Delay: 0-60 seconds,forward or reverse-acting
Supply Voltage: 13-30VDC
Power Consumption: 2 watts maximum
Output: 8 mA -Alarm 16 mA -Normal 22 mA -Fault
or
8 mA -Normal 16 mA -Alarm 5 mA -Fault
Housing: Dual Compartment,Powder-Coated aluminum with two cable entries
Cable Entry: M20 x 1.5 CENELEC 3⁄4-inch NPT FM/CSA
Ingress Protection: IP66 NEMA 4X |