| Loop Calibrator (Model 707) |
| Manufacturer: Fluke |
| |
| The fastest, one-handed tool for loop checks.
The Fluke 707 Loop Calibrator is a high performance solution for calibration, repair and maintenance of current loops. The new "Quick Click" knob making it extremely fast and easy to use. It features:
- One handed user interface with "Quick Click" detented knob
- mA sourcing, simulation and measurement
- 0.015% accuracy and 0.001 mA resolution
- Simultaneous mA and % of span display
- Selectable step or ramp outputs
- 24 V Loop supply with mA measure, including 250Ω HART resistor
- 0-28 VDC measurement to check Loop Voltage
- Easy battery exchange without opening the case
- Compact case with separate protective holster
- Three year warranty
This feature-rich solution combines the best features push-button and knob-base loop calibrator and offers:
- Large display and simple, quick-click interface for easy one-handed operation.
- Simultaneous mA and % readout for quick, easy interpretation of readings.
- mA accuracy of 0.015%, superior to other loop calibrators in this price range.
- 1 µA resolution for mA source, simulate and measure.
- Push button 25% steps for fast, easy linearity checks.
- 0-100% “span check” for fast confirmation of zero and span.
- Selectable slow ramp, fast ramp, and step ramp to provide smooth outputs for valve slewing and loop functional tests.
- 24 volt internal loop supply, so you can power and read a transmitter at the same time without carrying a DMM.
- Measures V dc to 28 V.
- Single 9V battery that is easily changed without braking calibration seal
- 0 - 20 mA or 4 - 20 mA default start up modes.
- Innovative output adjustment dial with 1 µA and 100 resolution.
- HART ™ mode connects 250 Ω resistor in series with 24 V loop for compatibility with HART communicators.
|
|
|
|
| |
| Specifications |
| Current Measurement |
| Range: |
0 to 24 mA |
| Resolution: |
0.001 mA |
| Accuracy: |
0.015% Rdg + 2 LSD |
|
| Current Sourcing |
| Range: |
0 to 20 mA or 4 to 20 mA |
| Accuracy: |
0.015% Rdg + 2 LSD |
| Drive Capability: |
1200 Ω; 950 Ω at 20 mA in HART mode |
|
| Current Simulation |
| Range: |
0 to 20 mA or 4 to 20 mA |
| Accuracy: |
0.015% Rdg + 2 LSD |
| Ext. loop voltage requirement: |
12-30 V |
|
| Loop Power |
|
| Voltage measurement |
| Range: |
0 to 28 V DC |
| Resolution: |
1 mV |
| Accuracy: |
0.015% Rdg + 2 LSD |
|
| Environmental Specifications |
| Operating Temperature |
|
| Storage Temperature |
|
| Humidity (Without Condensation) |
|
0 to 90% (0ºC to 35ºC); 0 to 70% (35ºC to 55ºC) |
|
| Temperature Coefficient |
|
-10ºC to 18ºC, 28ºC to 55ºC, ±.005% of range per ºC |
|
| Safety Specifications |
| Safety |
|
CSA C22.2 No. 1010.1:1992 |
|
| EMC |
|
EN50082-1:1992 and EN55022:1994 Class B |
|
| Maximum voltage |
|
| Mechanical & General Specifications |
| Size |
|
| Weight |
|
224 g (340 g including holster) |
|
| Batteries |
|
| Warranty |
|
| Shock & Vibration |
|
per MIL-T-28800 for a Class 2 Instrument |
|
| Display current and % of span |
|
| Auto step, auto ramp |
|
| Span Check |
|
|
|
 |
|