| Dual Line Flow Rate/Totalizers (Models PD6200 and PD6300) |
| Manufacturer: Precision Digital |
| |
|
| ProVu MODEL PD6200 ANALOG INPUT |
ProVu MODEL PD6300 PULSE INPUT
|
|
Analog Inputs
- 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
- Isolated 24 VDC @ 200 mA Transmitter Power Supply
- Open Channel Flow with Programmable Exponent
- Square Root Extraction
- 32-Point Linearization
|
Pulse Inputs (Available 3rd Quarter 2008)
- Pulse, Open Collector, NPN, PNP, TTL, Switch Contact, Square Wave Inputs
- 5, 10 or 24 VDC Excitation
- Gate Function for Rate Display of Slow Pulse Rates
- K-Factor, Internal Scaling or External Calibration
- 4-20 mA Output Option Converts the Pulse Input to an Isolated 4-20 mA Output
|
|
COMMON METER FEATURES
- NEMA 4X, IP65 Front
- Universal 85-265 VAC or 12/24 VDC Input Power
- Large Dual-Line 6-Digit Display, 0.60" & 0.46"
- Programmable Displays & Function Keys
- Sunlight Readable Display
- 2 or 4 Relays + Isolated 4-20 mA Output Options
- External 4-Relay & Digital I/O Expansion Modules
- RS-232, RS-422/485 Serial Communication Options
- -40 to 65°C Operating Temperature Range
|
COMMON RATE/TOTALIZER FEATURES
- Display Rate & Total at the Same Time
- Rate in Units per Second, Minute, Hour, or Day
- Total, Grand Total or Non-Resettable Grand Total
- Password Protection for Total Reset
- 9-Digit Totalizer with Total Overflow Feature
- Any Relay for Rate or Total
- 4-20 mA Output for Rate or Total
- Sampling Relay
- Total Stored in Non-Volatile Memory
|
|
|
|
FRONT PANEL DISPLAY
Display Flow Rate, Total or Grand Total
The main display can be programmed to display flow rate, total or grand total, and the secondary display can be programmed to display flow rate, total or grand total, engineering units, custom legends or can be turned off. Both displays could also display relay set points or max and min values.
In the graphic above, the main display is displaying flow rate (as indicated by the gRh to the right of the number) and the secondary display is displaying flow total (as indicated by the T under the number.) The following photographs show typical ways these flow rate/totalizers can be programmed:
Totalizer Overflow Displays Total to 9 Digits
These flow rate/totalizers can display up to nine digits of total flow with the total overflow feature. In the diagrams below, the flow totalizer is displaying 532,831,470 by toggling between a display of goF 532h and g831470h. Notice the (T with arrow £ symbol) is lit up indicating the display is in overflow mode.
|
|
Rugged
| A unique front panel design makes the ProVu nearly impenetrable in typical applications. Here, the ProVu easily survives a direct hit on the display from a heavy 2" solid stainless steel ball dropped from eight feet. |
 |
TOTALIZER CAPABILITIES
These ProVu flow rate/totalizers can be programmed for a wide variety of totalilzer applications. They can display total, grand total, or non-resettable grand total with a time base of seconds, minutes, hours or days. The user can program a totalizer conversion factor, a non-resettable grand total, password protection and several total reset methods.
Non-Resettable Grand Total
The user can set up the grand total to be non-resettable by entering a specific password. Once this is done, the grand total can never be reset.
Totalizer Conversion Factor
The user can enter a totalizer conversion factor that allows the meter to display total in different units than the rate. For instance, a customer could measure flow rate in gallons per minute and total in hundredths of acre-feet.
Password Protection
The total and grand total can be password protected so they can be reset only by authorized personnel.
 |
 |
| Total Password |
Grand total Password |
Front Panel Total Reset
The three front panel function keys can be programmed to reset the total and grand total. This makes it possible for the user to reset either the total or the grand total by pressing the appropriate function key. Of course, if the total or grand total is password protected, they will not reset when the function key is pressed. |
 |
|
| |
Remote Total Reset
An I/O expansion module can be used to remotely reset the total or grand total. The reset switch is wired into the module and the module is connected to the M-Link RJ45 socket at the back of the flow rate/totalizer.
Total Alarms
The ProVu’s four internal and four external relays can be set up to alarm when the total reaches a user-defined set point. A variety of reset modes are available and the user can also program time delays and fail safe operation.
FIELD EXPANSION MODULES
Add functionality to the ProVu in the field with easy-to-install external expansion modules. Add RS-232 or
RS-422/485 communications, I/O modules (up to 2), or 4-relay expansion module. The menu items for these modules do not appear until the module is connected, simplifying the basic menu. Relay and digital I/O modules
are shown below with optional DIN rail mounting kit, P/N PDA1002.
I/O Expansion Module
Four digital inputs and four digital outputs are available per expansion module. The ProVu meter will accept two of these modules. External digital inputs can function similarly to the front panel function keys. They can be configured to trigger certain events (i.e. reset total or grand total, acknowledge/reset alarms, reset max and/or min values, disable/enable all output relays, and hold current relay states), and provide direct menu access point.
Digital outputs can be used to remotely monitor ProVu’s alarm relay output states, or the states of a variety of actions and functions executed by the meter.
Relay Expansion Module
An external module containing four 3 amp Form A (SPST) relays can be added to the ProVu at anytime. Removable
screw terminal blocks accept 12 to 22 AWG wire.
|
 |
 |
Communications Module
Serial communications on the ProVu can be added anytime with external RS-232 or RS-422/485 communication adapters.
|
OUTPUTS
| Relay Outputs |
 |
| The ProVu has up to four 3 A Form C relays (SPDT), giving you more fail-safe options upon power loss. Relay action can also be configured for input loop break protection. Set ON and OFF delay times when needed. Up to eight front panel indicators show alarm and/or relay state. All relays can be configured for 0-100% deadband. |
Relay Operation & Configuration
There are powerful relay functions that can be configured in the meter, including:
Automatic reset only (non-latching)
Automatic + manual reset at any time (non-latching)
Latching (manual reset only)
Latching with clear (manual reset only after alarm condition has cleared)
Sampling (activated for a user-specified time)
User selectable fail-safe operation
Relay action for loss (break) of 4-20 mA input signal
Time delay (on and off), independent for each relay
Manual control mode
Analog Output
The isolated analog retransmission signal can be configured to represent the rate, total, grand total, maximum (peak) value, minimum (valley) value, or the value for any of the eight relay set points. While the output is nominally 4-20 mA, the signal will accurately accommodate ranges from 1 to 23 mA.
Auto/Manual Control
Take control of any output with this feature. All relays can be forced ON or OFF, and the 4-20 mA output signal can be set to any value within its range. This is particularly useful for valve control applications.
Isolated Transmitter Power Supplies
A powerful 24 V @ 200 mA power supply is a standard feature on the ProVu meter. It can be configured for 5, 10, or 24 V (default) by means of a simple internal jumper (see manual). An additional power supply (24 V @ 40 mA) is standard with the 4-20 mA output option.
NEMA 4 & 4X FIELD ENCLOSURES
Plastic, stainless steel, and painted steel NEMA 4X enclosures for up to 10 ProVu meters.
 |
 |
| PDA2811 |
PDA2706 |
|
EASY PROGRAMMING AND SETUP
Dual-Line Display & 4 Buttons
The user friendly dual-line display and four programming buttons make the ProVu easy to set up and program. The four buttons keep the user in control of the programming process, and the second line provides a reminder or prompt for the current programming step.
 |
 |
| Input 1 |
Display 1 |
The meter on the left is prompting the user to enter the desired input value, which in this case will be 4 mA. A key feature of the ProVu is that it is not necessary to actually apply this input so the meter can be scaled without a calibrator.
The meter on the right is prompting the user to enter the desired display value that corresponds to Input 1. The right arrow moves the active digit to the right and the up arrow increases the value of the digit.
I/O Module for Remote Programming
The I/O module can be used to program the ProVu remotely, in essence giving the user control of the four front panel push buttons. This feature is particularly useful if the meter is mounted inside an explosion-proof enclosure.
METER COPY
The Copy feature is used to copy (or clone) all the settings from one ProVu to other ProVu meters in about 20 seconds! The Copy function is a standard feature on all meters. It does not require a communications adapter, only an optional cable assembly, P/N PDA1200. See the ordering information for complete details.
Copying Meter Settings
APPLICATIONS
Open Channel Flow
The PD6200, in combination with an ultrasonic level transmitter, makes for an economical way to measure and display open channel flow rate and total in most weirs and flumes and take periodic samples. All the user needs to do is enter the exponent for the weir or flume into the PD6200 and the PD6200 automatically raises the input signal to that power. Sampling can be based on the total flow or the flow rate. For instance, to display open channel flow rate and total from a 3 inch Parshall flume and take a one pint sample every 100,000 gallons, the user would program the PD6200 as follows:
| Function |
Desire |
Programming |
| Open Channel Flow |
3" Parshall flume |
Set Programmable Exponent to 1.547 |
| Flow Rate |
Millions of Gallons per Day (MGD) |
Set 4 mA=0 & 20 mA=3.508
Time base=Day |
| Total |
Millions of Gallons |
Set Totalizer Conversion Factor=1
(password protect total reset) |
| Non-Resettable Grand Total |
Program meter so grand total can never be reset |
Set non-resettable grand total password |
| Display |
Display Flow Rate and Total at the same time |
Set main display for Grand Total and secondary display to toggle between rate and total |
| Sampling |
Take a 1 pint sample every 100,000 gallons |
Set up relay for sampling and to trip every 0.1 million gallons. Set up sampling time such that 1 pint is sampled |
Differential Pressure Flow
The PD6200 can display flow rate and total by extracting the square root from the 4-20 mA signal from a differential pressure transmitter. The user selectable low-flow cutoff feature gives a reading of zero when the flow rate drops below a user selectable value.
- Display Flow Rate
- User Selectable Low-Flow Cutoff
- Only 2 Calibration Points Required
|
Convert Pulse to 4-20 mA with PD6300
The PD6300 accepts the pulse output from a flowmeter and with the appropriate option installed can convert the pulse to a 4-20 mA signal. The 4-20 mA signal can be programmed to correspond to either the flow rate or the total flow.
CONNECTIONS
PD6200
PD6300
MOUNTING DIMENSIONS
Notes:
1. Panel cutout required: 1.772" x 3.622" (45mm x 92mm)
2. Panel thickness: 0.040 - 0.250" (1.0mm - 6.4mm)
3. Mounting brackets lock in place for easy mounting
4. Clearance: Allow 6" (152 mm) behind the panel |
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C
General
Display: Main display: 0.60" (15 mm) high, second display: 0.46" (12 mm) high. Both displays are 6 digits (-99999 to 999999), red LEDs with leading zero blanking
Display Intensity: Eight user selectable intensity levels
Overrange: Display flashes 999999
Underrange: Display flashes -99999
Front Panel: NEMA 4X, IP65
Programming Methods: Four front panel buttons, digital inputs, PC and multi-point linearization utility, or cloning using Copy function
Recalibration: All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months
Max/Min Display: Max (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power to the meter is turned off
Password: Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals. Pass 1: Allows use of the F1–F3 function keys. Pass 2: Allows use of the F1–F3 function keys and changing the set/reset points. Pass 3: Restricts all programming and F1–F3 keys. Total: Prevents resetting the total manually. Gtotal: Prevents resetting the grand total manually
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC 20 W max, or jumper selectable 12/24 VDC ±10%, 15 W max.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 5% @ 200 mA max (standard), (12/24 VDC powered models rated @ 100 mA max). 5 or 10 VDC @ 50 mA max, selectable with internal jumper J4
Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply
Environmental: Operating temperature range: -40 to 65°C. Storage temperature range: -40 to 85°C. Relative humidity: 0 to 90% non-condensing
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black
Mounting: 1/8 DIN panel cutout required: 3.622" x 1.772"(92 mm x 45 mm). Two panel mounting bracket assemblies are provided
Tightening Torque: Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall Dimensions: 4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Weight: 9.5 oz (269 g)
UL File Number: UL & c-UL Listed. E160849; 508 Industrial Control Equipment
Warranty: 3 years parts & labor
PD6200 Analog Inputs
Inputs: Field selectable: 0-20, 4-20 mA, ±10 VDC (0-5, 1-5, 0-10 V)
Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span
Display Update Rate: 5/second (200 ms)
Temperature Drift: 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient
Math Function: Linear, square root, programmable exponent, or round horizontal tank volume calculation
Multi-Point Linearization: 2 to 32 points
Programmable Exponent: 1.0001 to 2.9999
Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd
Calibration Range: Input range: 4-20 mA, ±10 V. Minimum span: 0.15 mA or 0.10 V. An Error message will appear if input 1 and input 2 signals are too close together
Input Impedance: Voltage ranges: greater than 1 MÙ. Current ranges: 50 - 100 Ù (depending on resettable fuse impedance)
Input Overload: Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed
Noise filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span
Normal Mode Rejection: Greater than 60 dB at 50/60 Hz
PD6300 Rate Inputs
Inputs: Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 kΩ pull-up to 3.3 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7 kΩ pull-up to 3.3 V @ 40 Hz
Low Voltage Mag Pickup (Isolated): Sensitivity: 125 mVp-p; Hysteresis: 30 mV (Order with MOD0077 for 20 mVp-p sensitivity)
Minimum Input Frequency: 0.0101 Hz. Minimum frequency is dependent on high gate setting
Maximum Input Frequency: 30,000 Hz
Input Impedance: Pulse input: Greater than 300 kΩ @ 1 kHz. Open collector/switch input: 4.7 kΩ pull-up to 3.3 V
Accuracy: ±0.03% of calibrated span ±1 count
Temperature Drift: Rate display is not affected by changes in temperature
Multi-Point Linearization: 2 to 32 points
Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
Decimal Point: Up to five decimal places or none: d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Calibration: May be calibrated using K-factor, scale using internal calibration, or calibrate by applying an external calibration signal
K-Factor: Field programmable K-factor converts input pulses to rate in engineering units. May be programmed from 0.00001 to 999,999 pulses/unit
Calibration Range: Input 1 signal may be set anywhere in the range of the meter; input 2 signal may be set anywhere above or below input 1 setting. Minimum input span between any two inputs is 10 Hz. An Error message will appear if the input 1 and input 2 signals are too close together
Filter: Programmable contact de-bounce filter: 40 to 999 Hz maximum input frequency allowed with low speed filter
Time Base: Second, minute, hour, or day
Gate: Low gate: 0.1-99.9 seconds; High gate: 2.0-999.9 seconds
Rate/Totalizer
Display Assignment: The main (Big) and small (Little) displays may be assigned to rate, total, grand total, alternate R & T, units, and set point
Rate Display Indication: 0 to 999999, lead zero blanking. “R” LED illuminates while displaying rate
Total Display & Total Overflow: 0 to 999,999; automatic lead zero blanking. “T” LED is illuminated while displaying total or grand total. Up to 999,999,999 with total-overflow feature. “oF” is displayed to the left of total overflow and ▲ LED is illuminated
Alternating Display: Either display may be programmed to alternate between rate and total or rate and grand total every 10 seconds
Total Decimal Point: Up to five decimal places or none: d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd. Total decimal point is independent of rate decimal point
Totalizer: Calculates total based on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed
Totalizer Rollover: Totalizer rolls over when display exceeds 999,999,999. Relay status reflects display
Total Overflow Override: Program total reset for automatic with 0.1 second delay and set point 1 for 999,999
Totalizer Presets: Up to eight, user selectable under setup menu. Any set point can be assigned to total and may be programmed anywhere in the range of the meter for total alarm indication
Programmable Total Reset Delay: 0.1 to 999.9 seconds; applied to the first relay assigned to total or grand total. If the meter is programmed to reset total to zero automatically when the preset is reached, then a delay will occur before the total is reset
Total Reset: Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications
Total Reset Password: Total and grand total passwords may be entered to prevent resetting the total or grand total from the front panel.
Non-Resettable Total: The grand total can be programmed as a non-resettable total by entering the password “050873”
Caution: Once the Grand Total has been programmed as “non-resettable” the feature cannot be disabled
|
|