Additional Features
Password Protection
A 5-digit password prevents unauthorized changes to the programmed parameter settings. The lock symbol is displayed to show that settings are protected. If the meter is password protected, the meter will display the message LOCKED when the Menu button is pressed.
Alarm Indication
The PD6800 has high or low alarm indication. When in alarm, the display will flash, and a HI or LO symbol is displayed. The alarm has an adjustable deadband (the difference between the set and reset points). The alarm is acknowledged by pressing the ENTER/ACK button.
Installation
Installation Flexibility
The PD6800's rotatable display/meter module along with two available conduit connections provide for numerous installation options. The display can be rotated in 90° increments. Rotate it 90° for horizontal mounting. Wiring can then be routed to either the top conduit connection, or from below to the opposite conduit connection (metal conduit plug supplied). Use both conduit connections for through-wiring in any plane.
Easy Wiring & Service
Unscrew the two captured thumb screws and unplug a connecting cable and the display/meter module is simply and completely removed. A heavy duty terminal block is then easily accessed and wired. It is clearly marked to prevent wiring errors. The display/meter module can be removed without breaking the loop. As such, it can be serviced without the need to uninstall the entire product.
Connections
To access the wiring connections, remove the enclosure cover and unscrew the two captive screws that fasten the display module. Disconnect the ribbon cable and remove the display module. Power and signal connections are made to a terminal block at the base of the enclosure. Grounding connections are made to the two ground screws provided on the base – one internal and one external.
Specifications
Except where noted all specifications apply to operation at +25°C.
General
Display: Upper: Five digits (-9999 to 99999) 0.70" (17.8 mm) high, 7-segment, automatic lead zero blanking. Lower: Seven characters 0.4" (10.2 mm) high, 14 segment alphanumeric. Symbols: for high & low alarm, Password Lock. Backlight: White
Decimal Point: Upper process display has up to four decimal places or none: d.dddd d.ddd, d.dd, d.d, or ddddd
Display Update Rate: Ambient > -25°C: 2 Updates/Second. Ambient < -25°C: 1 Update/5 Seconds
Display Orientation: Display may be mounted at 90° increments up to 270° from default orientation.
Overrange: Display flashes 99999
Underrange: Display flashes -9999
Programming Method: Four SafeTouch® through-glass buttons when cover is installed. Four internal pushbuttons when cover is removed.
Noise Filter: Programmable - Lo, Med, Hi, or Off
Recalibration: Recalibration is recommended at least every 12 months.
Max/Min Display: Max/Min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
Password: Programmable password restricts modification of programmed settings.
Advanced Functions: Live input calibration, linearization, square root, or programmable exponent
Alarm Indication: Flashing display plus HI/LO indicators
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Normal Mode Rejection: 64 dB at 50/60 Hz
Operating Temperature Range: -40 to 75°C.
Storage Temperature Range: -40 to 85°C.
Relative Humidity: 0 to 90% non-condensing
Connections: Screw terminals accept 12 to 22 AWG wire
Enclosure: Explosion-proof die-cast aluminum with glass window, corrosion resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Copper-free (0.3%). Two ¾" NPT threaded conduit openings. One ¾" NPT metal conduit plug with 12 mm hex key fitting installed.
Mounting: May be mounted directly to conduit. Two slotted flanges for wall mounting or NPS 1½" to 2½" or DN 40 to 65 mm pipe mounting.
Overall Dimensions: 5.65" x 5.25" x 4.86" (W x H x D) (144 mm x 133 mm x 124 mm)
Weight: 5.00 lbs (80 oz, 2.27 kg)
Warranty: 3 years parts and labor
Input
Input range: 4-20 mA
Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span.
Temperature Drift: 50 PPM/°C
Decimal Point: User selectable decimal point
Calibration Range: An error message will appear if input 1 and input 2 signals are too close together. Input Range: 4-20 mA. Minimum Span Input 1 & Input 2: 0.10 mA
Maximum Voltage Drop: 3.0 VDC @ 20 mA without loop-powered backlight. 6.0 VDC @ 20 mA with loop-powered backlight
Equivalent Resistance: 150 Ω @ 20 mA without loop-powered backlight. 300 Ω @ 20 mA with loop-powered backlight
Input Overload: Over current protection to 2 A max.
External Loop Power Supply:
| Voltage Range |
Maximum Power |
| 9-30 VDC |
9 VDC |
12 VDC |
24 VDC |
30 VDC |
| |
0.2 W |
0.25 W |
0.5 W |
0.75W |
Product Ratings & Approvals
FM: Explosion-proof for use in Class I, Division 1, Groups B, C, D. Class II, Division 1, Groups E, F, G. Class III, Division 1; T6. Class I, Zone 1, AExd IIC T6 Gb. Zone 21, AEx tb IIIC T85°C. Ta=-40 to 75°C.
Enclosure: Type 4X & IP66. Certificate number: 3040391
ATEX: II 2 G D. Ex d IIC T6 Gb. Ex tb IIIC T85°C Db IP68. Ta=-40 to 75°C.
Certificate number: Sira 10ATEX1116X
IECEx: IECEx SIR 10.0056X. Ex d IIC T6 Gb. Ex tb IIIC T85 C Db IP68. Ta=-40 to 75°C
CSA: Class I, Division 1, Groups B, C, D. Class II, Division 1, Groups E, F, G. Class III, Division 1; T6. Class I, Zone 1, Ex d IIC T6.
Ta=-40 to 75°C. Enclosure: Type 4X & IP66.
Certificate number: 11 2325749