The D1300 ADC module converts thermocouple temperature sensor input signals to digital information, linearizes the digital data, scales in either degrees C or F, and communicates the values to a host computer or PLC. The data values are transmitted in ASCII to a host computer via RS232 or RS485 .
The D1300 series modules can also be mounted on a DIN-Rail using the MK-1 mounting kit.
|
Overall Accuracy (error from all sources) from 0 to +40C ambient: +/-1deg C max (J,K,T,E types). +/-2.5 deg C max for (R,S,B,C types).
|
|
Resolution: 1 degree (C or F).
|
|
Common mode rejection: 100db at 50/60 Hz.
|
|
User selectable degrees C or F scaling.
|
|
Lead resistance effect: <20uV per 350 ohms
|
|
Input burnout protection to 250 VAC.
|
|
Input impedance: 100 megohm min.
|
|
Three open-collector digital outputs.
|
|
Open thermocouple indication.
|
|
Two digital inputs, one with 60 Hz events counter (D1300M series does not contain Events Counter).
|