The D1400 ADC module converts RTD temperature sensor input signals to digital information, linearizes the digital data, scales in either degrees C or F, and communicates the values to a host computer or PLC. The data values are transmitted in ASCII to a host computer via RS232 or RS485 .
The D1400 series modules can also be mounted on a DIN-Rail using the MK-1 mounting kit.
|
Accuracy: +/-0.3 deg C.
|
|
Resolution: 0.1 degree (C or F).
|
|
Common mode rejection: 100db at 50/60 Hz.
|
|
User selectable degrees C or F scaling.
|
|
Input connections: 2,3, or 4 wire.
|
|
Excitation current: 0.25mA.
|
|
Max lead resistance: 50 ohms
|
|
Input protection to 120Vac.
|
|
Automatic linearization and lead compensation.
|
|
One open collector digital output (or LO Alarm).
|
|
Ranges:
|
|
0.00385=-200 to +850C
|
|
0.00392=-200 to +600C
|
|
0.00388=-100 to +125C
|