The DIN-145 Thermistor input Modbus modules convert analog input signals to digital data and transmit via RS-485 using the Modbus RTU protocol for communication. The modules perform all signal conditioning, scaling, thermistor linearization and conversion to either linearized ASCII data values or Modbus percent of full scale binary values.
|
Thermistor Input: 2252 ohms at 25 C, TD Series.
|
|
Ranges: 2252=-0 C to +100 C.
|
|
TD=-40 C to +150 C.
|
|
Resolution: 2252=0.01 C or F.
|
|
TD=0.1 C or F.
|
|
Accuracy: 2252=+/-0.1 C.
|
|
Common mode rejection: 100dB at 50/60Hz.
|
|
Input burnout protection to 30Vdc.
|