Utility Multimeter (113)
Fabricant: Fluke
 
Prix: $150.00 (USD)
Stock Status: 2 à 3 semaines
True-rms Utility Multimeter designed for basic electrical tests

The Fluke 113 Utility Multimeter gives utility users the means to quickly and easily do basic meter set and reconnect testing. This meter is simple-to-use and has the features needed to repair most electrical problems. The Fluke 113 has significant improvements over Fluke¡¯s original 7-600, and other utility multimeters. Using the Fluke VCHEK¢â LoZ low impedance measurement function, users can simultaneously test for voltage or continuity. The Fluke 113 can perform diode tests, and also provides both auto and manual ranging capabilities. With features such as conformance to the latest safety standards, backlight, and a much larger display that¡¯s easier to view, this new meter is a must have for the utility users toolbox.

Features and benefits of the Fluke 113

  • VCHEK¢â LoZ low impedance measurement function to simultaneously test for voltage or continuity
  • True-rms for accurate ac measurements on non-linear loads
  • A large backlit display allows for easy visibility in low-lit areas
  • Record signal fluctuations using the Min/Max function
  • Diode test for testing general-purpose germanium, silicon, and power diodes
  • Integral holster with probe holders for easy storage
  • Auto and Manual ranging for added user functionality
  • Meets Measurement Category CAT III 600 V and Category IV 300 V standards for a higher level of safety
  • The optional TPAK magnetic hanger allows the user hands-free flexibility

Utility Multimeter
 
Specifications
VCHECK 1,2
Range 6.000 V
60.00 V
600.0 V
Resolution 0.001 V
0.01 V
0.1 V
Accuracy DC, 45 to 500 Hz:2.0 % + 3
500 Hz to 1 kHz: 4.0 % + 3
Diode test 3
Range 2.000 V
Resolution 0.001 V
Accuracy 2.0 % + 3
Continuity3
Range
Resolution
Accuracy Beeper on < 20 ¥Ø, off > 250 ¥Ø; detects opens or shorts of 500 ¥ìs or longer
§Ù3
Range 600.0 ¥Ø
6.000 k¥Ø
60.00 k¥Ø
Resolution 0.1 ¥Ø
0.001 k¥Ø
0.01 k¥Ø
Accuracy 0.9 % + 2
0.9 % + 1
0.9 % + 1
Capacitance3
Range 1000 nF
10.00 ¥ìF
100.0 ¥ìF
9999 ¥ìF
Resolution 1 nF
0.01 ¥ìF
0.1 ¥ìF
1 ¥ìF
Accuracy 1.9 % + 2
1.9 % + 2
1.9 % + 2
100 ¥ìF - 1000 ¥ìF: 1.9 % + 2
> 1000 ¥ìF: 5 % + 20

Notes:
1 All VChek voltage ranges are specified from 60 counts to 100 % of range. Because inputs below 60 counts are not specified, it is possible and normal for this and other true-rms meters to display non-zero readings when the test leads are disconnected from a circuit or are shorted together.
2 Crest factor of ¡Â 3 at 4000 counts, decreasing linearly to 1.5 at full scale.
3 After measuring voltage, a wait time of 1 minute is required to maintain accuracy of ohms, capacitance, diode test, and continuity.

Specifications
Maximum voltage between any terminal and earth ground
600 V
Display
3 3/4-digits, 6000 counts, updates 4/sec
Operating temperature
-10 ¡ÆC to 50 ¡ÆC (14 ¡ÆF to 122 ¡ÆF)
Storage temperature
-40 ¡ÆC to 60 ¡ÆC (-22 ¡ÆF to 140 ¡ÆF)
Temperature coefficient
0.1 x (specified accuracy)/¡ÆC (< 18 ¡ÆC or > 28 ¡ÆC)
Operating altitude
2,000 m
Storage altitude
10,000 m
Relative humidity
95 % to 30 ¡ÆC
75 % to 40 ¡ÆC
45 % to 50 ¡ÆC
Battery type
9 Volt Alkaline, ANSI 1604A / IEC 6F22
Battery life
Alkaline: 300 hours typical, without backlight
Shock
1 Meter drop per IEC 61010-1-2001
Vibration
Per MIL-PRF-28800 for Class 2 instrument
Size (HxWxL)
167.1 mm X 85.1 mm X 46.0 mm (6.58 in X 3.35 in X 1.81 in)
Weight
13.0 oz (404 g)
Safety
Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 No 61010-1-04, UL 61010-1 (2004) and IEC/EN 61010-1 2nd Edition for measurement Category III, 600 V, Pollution Degree 2, EMC EN61326-1
EMI regulations
Complies with FCC Part 15, Class B

Specifications
VCHECK
Input Impedance (Nominal) ~3 k¥Ø < 300 pF
VCHECK
Common Mode Rejection Ratio (1 k¥Ø Unbalanced) > 60 dB at dc, 50 or 60 Hz
¥Ø
Open Circuit Test Voltage < 2.7 V dc
Full Scale Voltage < 0.7 V dc
Diode test
Open Circuit Test Voltage < 2.7 V dc
Full Scale Voltage 2.000 V dc
§Ù
Short Circuit Current < 350 ¥ìA
Diode test
Short Circuit Current < 1.0 mA

 Ressources
Fichier PDF – requiert Adobe Reader Instruction Sheet
Fichier PDF – requiert Adobe Reader Supplement Instruction Sheet
 Informations
 No. de pièce: Voir no. de pièce
 L'historique de votre navigation
 Utility Multimeter
 Insulation Multimeters
 Digital Multimeters
 Power Quality Clamp Meter
 Fluke 330 Series Clamp Meters
Copyright © 2012 Alpha Contrôles et Instrumentation Inc..  Tous droits réservés.