The HF5 transmitter is designed for fixed installation in either HVAC or industrial applications. The key features of the HF5 will satisfy application requirements ranging from the most basic to demanding. Selecting the appropriate probe model from the HF5 probe options is done based on the application. Depending on the probe model, the measuring range is within 0 to 100 %RH and -100 to 200°C (-148 to 392°F). The HygroClip 2 probes feature durable sensors and consistent performance. All HygroClip 2 probes can be hot-swapped to facilitate routine calibrations.
The HF5 transmitter is available in different configurations and has an extensive set of settings and functions that can be configured and enabled by the user with the ROTRONIC HW4 software.
In spite of its sophistication, the HF5 can still be used just as a simple conventional humidity and temperature transmitter. Whether you decide or not to take advantage of its full potential, the HF5 will let you have it your way.
Key Features
► Measures relative humidity and temperature
► Calculates dew point, frost point, wet-bulb temperature, mixing ratio, etc.
► Interchangeable probe - can be separated from transmitter by up to 5 m / 16.4 ft (100 m / 330 ft with a signal booster).
► Operating limits at probe 0 to 100 %RH and -100 to 200 °C (-148 to 392 °F) - depending on probe model
► Accuracy at 23 °C: ± 0.8 %RH and 0.1 °C
► 2-wire, loop-powered and 3-wire models
► Supply voltage: 10 to 28 VDC (2-wire models) or 15 to 40 VDC / 12 to 28 VAC (3-wire models)
► Optional LC display and keypad
► Analog signals only / Analog signals + Digital interface / Digital interface only
► Digital interface allows the simultaneous reading of relative humidity, temperature and calculated parameter
► Configurable analog output signals (signal type, parameter and range)
► Automatic RH sensor test with optional sensor drift correction 1)
► Configurable fail safe mode - fixed output signals in the event of a humidity or temperature sensor failure
► Simulator function (fixed output signals) for on-site validation of the measurement loop
► Full access to the settings and functions via external service connector or via optional digital interface