| Vous n’êtes pas loguer. SVP cliquez ici pour vous loguer. |
|
|
| |
 |
| Flush-Mount Room Pressure Monitor (SRCM) |
| Fabricant: Setra |
| |
Applications
- Hospital Patient Isolation Wards
- Pharmaceutical Manufacturing
- Semiconductor Fabs
- Cleanrooms
- Research Laboratories
- Animal Resource Facilities
| Model SRCM Specifications |
| Accuracy (at constant temperature) |
±0.25% or ±0.5%
|
| Operating Temperature |
32 to 120°F (0 to +50°C)
|
| Storage Temperature |
-20 to 160°F (-30 to +70°C)
|
| Operating Humidity |
5 to 95% RH (Non-condensing)
|
| Excitation/Output |
24 VAC/4 to 20 mA or
0 to 5 and 0 to 10 VDC
|
| Inputs |
1 Internal Pressure Sensor
2 A/D's inputs for remote pressure sensors
1 Digital Input |
| Alarm Output |
SPDT Relay
0.6A @ 120 VAC
2A @ 30 VDC |
| Communication Option |
BACnet MS/TIP ASC |
| Excitation/Output w/BACnet Option |
24 VAC
|
| Display |
LCD 4.3" TFT, 480 x 272, Dimmable |
| Room Condition Banners |
Green="Clear to Enter"
Yellow ="Caution"
Red="Do Not Enter" |
| Bidirectional Ranges |
±0.05, ±0.10, ±0.25, ±0.50, ±1.00, ±2.50, ±5.00 in. W.C.
±25, ±50, ±100, ±250, ±500, ±1000 Pa
|
| Electrical Connection |
Removable Terminal Block |
| Mounting |
Mounts to triple gang double deep electrical box. |
| Certifications |
|
CE
|
Electro-magnetic Compatibility Directive 2004/108 EC
|
|
|
| |
|
 |
|