Vous n’êtes pas loguer. SVP cliquez ici pour vous loguer.
FAIL (the browser should render some flash content, not this).
Transmetteur très basse pression différentielle (Model 265)
Fabricant: Setra
At ±1.0% Full Scale accuracy (±0.4%, ±0.25% FS optional), Setra's Model 265 provides superior positive and negative pressure sensing required for high efficiency, air-control systems. An optional snap-on conduit enclosure, molded from high impact Lexan®, is avaialble.
Applications
HVAC Equipment
Energy Management
Variable Air Volume (VAV)
Environmental Pollution Control
Static Duct & Clean Room Pressures
Oven Pressurization & Furnace Draft Controls
Medical Instrumentation
Model 265 Specifications
Electrical Output Voltage
0 to 5 VDC
Bidirectional Output (Voltage) at Zero
2.5 VDC
Electrical Output Current
4 to 20 mA
Accuracy (RSS Method)
±1.0% FS (Optional Accuracies: ±0.4%, ±0.25%)
Type of Pressure
Very Low Differential Pressure
Pressure Ranges
Unidirectional: 0 to 0.25, 0.5, 1.0, 2.5, 5.0, 10, 25, 50, 100 in.WC Bidirectional: 0 to ±0.1, ±0.25, ±0.5, ±1.0, ±2.5, ±5.0, ±10, ±25, ±50 in.WC
Thermal Effects
Thermal Compensation °F (°C):
0 to +150 (-18 to +65)
Zero/Span Shift %FS/°F (°C):
0.033 (0.06)
Media
Typically air or similar non-conducting gases
Click here for data sheet Model 265
* Specifications subject to change without notice. If you don't see what you need here, please contact us.