` 1662 Multifunction Installation Tester

Fluke

1662 Multifunction Installation Tester

Reliable, simple operation and all the testing power you need for day-in, day-out installation testing


$2,175.00 CAD
Normally ships in 4-6 Weeks

 
  Request Quote

Can We Help You?

CALL US   EMAIL US   CHAT LIVE

Our product experts are here to help you find the right solution for your application!

The Fluke 1662 installation tester gives you Fluke reliability and all the basic testing power you need for day-in, day-out installation testing. It tests to all local regulations and is easy and intuitive to use. Additional helpful features like the On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.

• Tests voltage and frequency
• Checks wiring polarity to detect broken N wires
• Measures insulation resistance and loop and line resistance
• Measures motor windings with continuity test
• Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)

AC Voltage Measurement

Range

500 V

Resolution

0.1 V

Accuracy (45 Hz - 66 Hz)

0.8% + 3

Input Impedance

360 kΩ

Overload Protection

660 Vrms

Continuity Testing (RLO)

Range (Autoranging)

20 Ω, 200 Ω, 2000 Ω

Resolution

0.01 Ω, 0.1 Ω, 1 Ω

Open Circuit Voltage

> 4 V

Insulation Resistance Measurement (RISO)

Accuracy of tTest Voltage (at Rated Test Current)

+10%, -0%

Test Voltage

100 V, 250 V, 500 V, 1000 V

Insulation Resistance Range

20 MΩ / 50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ

Resolution

0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ

Test current

1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ

Loop and Line Impedance (ZI)

Range

10 Ω, 0.001 Ω, high current mΩ mode

Resolution

0.01 Ω, 0.1 Ω, 1 Ω

Prospective Earth Fault Current, PSC Test

Range

1000 A, 10 kA (50 kA)

Resolution

1 A, 0.1 kA

Computation

Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.

RCD Testing, RCD Types Tested

RCD Type

A4, AC¹, G², S³

¹Responds to AC
²General, no delay
³Time delay
4Responds to pulsed signal
5Responds to smooth DC signal

Tripping Speed Test (ΔT)

Current Settings¹

10-30-100-300-500-1000 mA – VAR
10-30-100 mA

Multiplier

x 1/2, x 1
x 5

Measurement Range

RCD Type G

310 ms
50 ms

RCD Type S

510 ms
160 ms

¹1000 mA type AC only
700 mA maximum type A in VAR mode
VAR mode not available for type B.

RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)

Current Range

30% to 110% of RCD rated current¹

Step Size

10% of IΔN²

Dwell Time

Type G

300 ms/step

Type S

500 ms/step

Measurement Accuracy

+/- 5%

Specified Trip Current Ranges (EN 61008-1)

50% - 100% for Type AC
35% - 140% for Type A (> 10 mA)
35% - 200% for Type A (≤ 10 mA)
50% - 200% for Type B
²5% for Type B

¹30% - 150% for Type A IΔN > 10 mA
30% - 210% for Type A IΔN = 10 mA
20% - 210% for Type B

General Specifications

Size (L x W x H)

10 cm x 25 cm x 12.5 cm

Weight (Including Batteries)

1.3 kg

Battery Size, Quantity

Type AA, 6 ea.

Sealing

IP-40

Safety

Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition

Overvoltage

CAT III / 500V; CAT IV 300V

Performance

EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition