Skip to main content
Press Enter
Burns Engineering

200A/200B Direct & Variable Immersion Platinum RTDs

General purpose direct and variable immersion platinum RTDs, available with M12 connector (200A), -196°C to 500°C

Have questions? We're here to help!
Have questions? We're here to help!

A direct immersion style RTD that features a 1/2″ NPT process connection and 1/2″ NPT instrument connection. The 1/4″ diameter stem is standard with an optional 3/16″ diameter available. Pressure rated to 3000 psi. Available with ratings for use in hazardous atmospheres. Single element with 3 or 4 wire circuit or dual 3 wire sensing elements.

A direct immersion style RTD that features field adjustable immersion length via a 316 SS compression fitting with PTFE or SS ferrules. PTFE allows for readjustment of the immersion length. Add the HD04 connection head for a convenient and durable method of attaching your extension cable. Other heads and indicators can also be added.

Sensor type RTD (Pt100)
Temperature range -196 to 500 C (-320.8 to 932 F)
Sensor style Direct Immersion
Sheath diameter 0.25", 0.188"
Immersion depth Fixed
Process connection 200A: 1/2" NPT
200B: None
Head connection NPT
Spring loaded for thermowell No
Wire termination Head
Hazardous rating Optional
  • Thumbnail of document Data Sheet - 200A/200B Direct & Variable Immersion Platinum RTDs
    Download

    Data Sheet - 200A/200B Direct & Variable Immersion Platinum RTDs

    Download

Request a Service Quote

Get a customized quote for calibration, validation, repair, or training services designed to keep your instruments accurate and compliant.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more