The SharpEye 40/40C-M, a multispectrum QuadSense IR flame detector, provides long distance detection of hydrocarbon and hydrocarbon fires at up to 215 ft. (65 m), fast detection in under five seconds.
| Detection response time | Standard response: Typically < 5 sec |
| Sensitivity ranges | 5 sensitivity ranges for 1 ft2 (0.1 m2) n-heptane pan fire |
| Field of view | For hydrogen, horizontal: 90 °; vertical: 90 ° For other fuel, horizontal: 80 °; vertical: 80 ° |
| Temperature range | Operating: -40 °F (-40 °C) to 167 °F (75 °C) Storage: -40 °F (-40 °C) to 167 °F (75 °C) |
| Humidity | Non-condensing relative humidity up to 100% |
| Electrical Specifications | |
| Operating voltage | 24 Vdc nominal (18-32 Vdc) |
| Power consumption | Standby: Maximum 3 W (8 W with heated window) Alarm: Maximum 4.2 W (9 W with heated window) |
| Cable entries | 2 x ¾ in - NPT conduits or 2 x M25 x 1.5 mm ISO |
| Electrical input protection | According to EN 50130 |
| Electromagnetic compatibility | EMI/RFI protected to EN61000-6-3 and EN 50130 |
| Electrical interface | The detector includes 17 terminals and one wiring option |
| Outputs | |
| Relays | Alarm, fault, and auxiliary SPST volt-free contacts rated 2 A at 30 Vdc |
| Analog output | Analog port malfunction: 0 V (< 0.5 V) Normal: 2 V ± 0.3 V Alarm: 5 V ± 0.3 V |
| 0-20 mA (stepped) | Fault: 0 ± 1 mA Built-in test (BIT) fault: 2 mA ± 0.3 mA Normal: 4 mA ± 0.3 mA Warning: 16 mA ± 0.3 mA Alarm: 20 mA ± 0.3 mA |
| HART® protocol | HART communications on the 0-20 mA analog current (FSK)used for maintenance, configuration changes, and assetmanagement, available in mA source output wiring options |
| RS-485 | RS-485 Modbus® compatible communication link that can beused in computer controlled installations |
| Mechanical Specifications | |
| Enclosure options | Heavy duty copper free aluminum (less than 1%), polyurethanepainted |
| Mounting | Electropolished stainless steel 316 |
| Dimensions | Detector: 4 x 4.6 x 6.18 in (100.6 x 117 x 155 mm) |
| Weight | Detector aluminum: 2.8 lb (1.3 kg) Tilt mount: 2.5 lb (1.1 kg) |
| Water and dust | IP66 and IP68 per EN 60529, NEMA® 250 6P |
View All Part Numbers