` 40/40D-L4B SharpEye

Spectrex Inc.

40/40D-L4B SharpEye

Ultra-fast UV/IR flame detector

Call Today!
800-567-8686 Normally ships in 4-6 Weeks

  Request Quote

Can We Help You?

CALL US   EMAIL US   CHAT LIVE

Our product experts are here to help you find the right solution for your application!

The SharpEye 40/40D-L4B, an ultra-fast UV/IR flame detector, provides exeptional detection of hydrocarbon-based fuel and gas fires in under 20 msec. Featuring a unique dual sensor with selectable UV and IR channels that can be used separately or combined, widest operation temperature range in extreme weather conditions with unparalleled reliability to ensure a SharpEye on your safety!

• 20 msec Ultra Fast detection
• Proven false alarm immunity
• Unparalled reliability - 150,000 hours MTBF
• Best in class temperature range: -76 to +185 °F (-60 to +85 °C)
• Worldwide and regionally certified for hazardous areas
• Performance and reliability approved by recognable certification bodies
• SIL3 compatible
• Enhanced durability backed up by with five-year warranty
• Smart field of view integrity test, allowing flawless operation
• Innovative UV & IR Built-In-Test - continiously validating the optical integrity and the electronic circuitry
• Multiple output options for maximum compatibility with standard infrastructures
• Plug-and-Play - factory calibrated for immediate use in any fire detection system
• Universal wiring option for fast ordering process
• Three sensitivity levels, adapting to any application
• Two mode heated optics for impeccable performance in challenging environmental conditions
• Internal log event recorder to analyze past events

Detection response time Standard response: Typically 5 sec at 93 ft (28 m)Ultra fast response: 20 msec for flash fire pan fire from 10 ft(3 m) distanceHigh speed response (explosion): 50 msec for 1 ft (0.30 m)diameter sphere LPG-air mixture explosion at 32.8 ft (10 m)distance via analog voltage output
Sensitivity ranges 3 sensitivity ranges for 1 ft2 (0.1 m2) n-heptane pan fire
Field of view Horizontal: 100 °
Vertical: 95 °
Temperature range Operating: -76 °F (-60 °C) to 185 °F (85 °C)(1)
Storage: -76 °F (-60 °C) to 185 °F (85 °C)(1)
Humidity Non-condensing relative humidity up to 100%
Electrical specifications
Operating voltage 24 Vdc nominal (18-32 Vdc)
Power consumption Standby: Maximum 3 W (8 W with heated window)
Alarm: Maximum 4.2 W (9.6 W with heated window)
Cable entries 2 x ¾-in - 14 NPT conduits or 2 x M25 x 1.5 mm ISO
Electrical input protection According to EN 50130
Electromagnetic compatibility EMI/RFI protected to EN61000-6-3 and EN 50130
Electrical interface The detector includes 17 terminals and one wiring option
Outputs
Relays Alarm, fault, and auxiliarySPST volt-free contacts rated 2A at 30 Vdc
Analog output Analog port malfunction: 0 V (< 0.5 V)
Normal: 2 V ± 0.3 V
Alarm/explosion: 5 V ± 0.3 V
0-20 mA (stepped) Fault: 0 ± 1 mA
Built-in test (BIT) fault: 2 mA ± 0.3 mA
Normal: 4 mA ± 0.3 mA
Warning: 16 mA ± 0.3 mA
Alarm: 20 mA ± 0.3 mA
HART® protocol HART communication on the 0-20 mA analog current (FSK)used for maintenance, configuration changes, and assetmanagement, available in mA source output wiring options
RS-485 RS-485 Modbus®-compatible communication link that can beused in computer controlled installations
Mechanical specifications
Enclosure options Electropolished stainless steel 316
Heavy duty copper free aluminum (less than 1%), polyurethanepainted

• Oil & gas onshore and offshore installations and pipelines 
• Chemical and petrochemical plants 
• Storage tank farms 
• Fuel and gas processing and storage facilities 
• Power generation 
• Explosives and munitions 
• Fertilizer plants 
• Automotive industry 
• Vehicle battery charging stations 
• Hydroxyl production and storage 
• Aerospace industry 
• Waste management facilities 
• Pharmaceutical industry 
• Printing 
• Hazardous materials storage areas 
• Food processing



Your Recently Viewed Items...