Detects fuel and gas fires at long distances with the highest immunity to false alarms, 5 year warranty
The 40/40I, a multi spectrum based on three IR bands (IR3), detects fuel and gas fires at long distances with the highest immunity to false alarms. The 40/40I IR3 can detect a 1ft2 (0.1 m2) gasoline pan fire at 215 ft (65m) in less than 5 seconds.
The 40/40I is the most durable and weather resistant flame detector currently on the market. Its new features include a heated window, to eliminate condensation and icing; HART capabilities for digital communications; lower power requirements; and a compact, lighter design.
• Multi Spectrum Design - for long distance detection and high false alarm immunity
• Sensitivity Selection - to ensure no zone crossover detection
• Automatic and Manual Built-In-Test (BIT) - to assure continued reliable operation
• Heated Window - for operation in harsh weather conditions (snow, ice, condensation)
• Multiple Output Options for maximum flexibility and compatibility
- Relays (3) for Alarm, Fault and Auxiliary
- 0-20mA (stepped)
- HART Protocol for maintenance and asset management
- RS-485, Modbus Compatible
• High Reliability - MTBF - minimum 150,000 hours
• Approved to Safety Integrity Level 2 (SIL2 – TUV)
• 5-Year Warranty
• User Programmable via HART or RS-485
• Hazardous area zones:
- Zones 1 & 2 with IIC gas group vapors present
- Zones 21 & 22 with IIIC dust type present
• Ex approved to:
- ATEX & IECEx
- FM/FMC/CSA
• 3rd party Performance Tested
- EN54-10 (VdS)
- FM3260
• Marine Approval
- MED "Wheelmark" approval (DNV)
Spectral Response | Three IR Bands |
Detection Range (at highest Sensitivity Setting for 1ft2 (0.1m2) pan fire) | Fuel ft / m n-Heptane 215 / 65 Gasoline 215 / 65 Diesel Fuel 150 / 45 JP5 150 / 45 Kerosene 150 / 45 Ethanol 95% 135 / 40 Methanol 115 / 35 IPA (Isopropyl Alcohol) 135 / 40 Methane* 150 / 45 LPG* 150 / 45 Polypropylene Pellets 115 / 35 Office Paper 83 / 25 * 30" (0.75m) high, 10" (0.25m) width plume fire |
Response Time | Typically 5 seconds |
Adjustable Time Delay | Up to 30 seconds |
Sensitivity Ranges | 4 Sensitive ranges for 1 ft2 (0.1m2) n-heptane pan fire from 50 ft (15m) to 215 ft (65m) |
Field of View | Horizontal 100º; Vertical 95º |
Built-in-Test (BIT) | Automatic (and Manual) |
Temperature Range | Operating: -67ºF to +167ºF (-55ºC to +75ºC) Option: -67ºF to +185ºF (-55ºC to +85ºC) Storage: -67ºF to +185ºF (-55ºC to +85ºC) |
Humidity | Up to 95% non-condensing (withstands up to 100% RH for short periods) |
Heated Optics | To eliminate condensation and icing on the window |
Hazardous Area Ex Approvals: ATEX approval remark , IECEx approval remark , FM approval remark , FMC approval remark , CSA approval remark , CU TR approval remark , CIMFR approval remark
Functional Approvals: FM approval remark , FMC approval remark , EN54-10 approval remark , CPD approval remark
Reliability Approvals: SIL2 approval remark
Other Approvals: Marine Equipment Directive approval remark , MED-D approval remark , MED-B approval remark
Spectrex 40/40I Triple IR (IR3) Flame Detector - Data Sheet 169.5 KB |
Spectrex 40/40I Triple IR (IR3) Flame Detector - Manual 2.1 MB |