Detects hydrocarbon-based fuel and gas fires using advanced flame analysis tools, 5 year warranty
The 40/40R Single IR Flame Detector detects hydrocarbon-based fuel and gas fires using advanced flame analysis tools. The detector provides early warning of flaming fires working at 4.5 μm for maximum sensitivity, and immunity to false alarms from IR sources such as sunlight and IR projectors.
The 40/40R is the most durable and weather resistant single IR flame detectors currently on the market. Its new features include a heated window, to eliminate condensation and icing; HART capabilities, for digital communications; lower power requirements; and a compact, lighter design.
• Sensitivity selection
• Automatic and Manual Built-In-Test (BIT) - to assure continued reliable operation
• Heated Window - for operation in harsh weather conditions (snow, ice, condensation)
• Multiple Output Options for maximum flexibility and compatibility
- Relays (3) for Alarm, Fault and Auxiliary
- 0-20mA (stepped)
- HART Protocol for maintenance and asset management
- RS-485, Modbus Compatible
• High Reliability - MTBF - minimum 150,000 hours
• Approved to Safety Integrity Level 2 (SIL2 - TUV)
• 5-Year Warranty
• User Programmable via HART or RS-485
• Hazardous area zones:
- Zones 1 & 2 with IIC gas group vapors present
- Zones 21 & 22 with IIIC dust type present
• Ex approved to:
- ATEX & IECEx
- FM/FMC/CSA
• 3rd party Performance Tested
- EN54-10 (VdS)
- FM3260
Spectral Response | Single band IR 4.4-4.6 μm |
Detection Range (at highest Sensitivity Setting for 1ft2 (0.1m2) pan fire) | Fuel ft / m n-Heptane 50 / 15 Gasoline 50 / 15 Diesel Fuel 37 / 11 JP5 37 / 11 Kerosene 37 / 11 Ethanol 95% 25 / 7.5 Methanol 25 / 7.5 IPA (Isopropyl Alcohol) 25 / 7.5 Methane* 29.5 / 9 LPG* 43 / 13 Polypropylene Pellets 37 / 11 Office Paper 20 / 6 * 30" (0.75m) high, 10" (0.25m) width plume fire |
Response Time | Typically 5 seconds |
Adjustable Time Delay | Up to 30 seconds |
Sensitivity Ranges | 2 ranges; 1 ft2 (0.1m2) n-heptane pan fire from 15 ft (5m) or 50 ft (15m) |
Field of View | Horizontal 90º; Vertical 90º |
Built-in-Test (BIT) | Automatic (and Manual) |
Temperature Range | Operating: -67ºF to +167ºF (-55ºC to +75ºC) Option: -67ºF to +185ºF (-55ºC to +85ºC) Storage: -67ºF to +185ºF (-55ºC to +85ºC) |
Humidity | Up to 95% non-condensing (withstands up to 100% RH for short periods) |
Heated Optics | To eliminate condensation and icing on the window |
Hazardous Area Ex Approvals: ATEX approval remark , IECEx approval remark , FM approval remark , CSA approval remark , CU TR approval remark , CIMFR approval remark
Functional Approvals: FM approval remark , EN54-10 approval remark , CPR approval remark
Reliability Approvals: SIL2 approval remark
Other Approvals: CAL FIRE approval remark
Spectrex 40/40R Single IR Flame Detector - Data Sheet 166.4 KB |
Spectrex 40/40R Single IR Flame Detector - Manual 2 MB |