Detects hydrocarbon-based fuel and gas fires, invisible hydrogen flames, and fires from hydrides, ammonia, silane and other organics
The new 40/40 UV Flame Detector detects hydrocarbon-based fuel and gas fires, invisible hydrogen flames, and fires from hydrides, ammonia, silane and other organics. The 40/40U-UB is the most durable and weather resistant UV flame detector currently on the market. Its new features include a heated window to eliminate condensation and icing; HART capabilities, for digital communications; lower power requirements; and a compact, lighter design.
Due to increased reliability, the 40/40 Series warranty period has been extended to 5 years and is SIL2 (TUV) approved to IEC 61508.
The model 40/40UB includes a Built-in-Test (BIT) feature, whereas the 40/40U model does not.
Note: This type of detector should not be exposed to UV radiation sources such as welding, sparks, and electric arcs as it will cause false alarms.
• UV spectrum design
• Automatic and Manual Built-In-Test (BIT) - to assure continued reliable operation (in 40/40UB only)
• Heated Window - for operation in harsh weather conditions (snow, ice, condensation)
• Multiple output options for maximum flexibility and compatibility
- Relays (3) for Alarm, Fault and Auxiliary
- 0-20mA (stepped)
- HART Protocol for maintenance and asset management
- RS-485, Modbus Compatible
• High Reliability - MTBF - minimum 150,000 hours
• Approved to Safety Integrity Level 2 (SIL2 - TUV) - Model 40/40UB only
• 5-Year Warranty
• User Programmable via HART or RS-485
• Hazardous area zones:
- Zones 1 & 2 with IIC gas group vapors present
- Zones 21 & 22 with IIIC dust type present
• Ex approved to:
- ATEX & IECEx
- FM/FMC/CSA
• 3rd party Performance Tested
- EN54-10 (VdS)
- FM3260
Spectral Response | UV 0.185-0.260 μm |
Detection Range (at highest Sensitivity Setting for 1ft2 (0.1m2) pan fire) | Fuel ft / m n-Heptane 50 / 15 Gasoline 50 / 15 Diesel Fuel 37 / 11 JP5 37 / 11 Kerosene 37 / 11 Ethanol 95% 37 / 11 Methanol 25 / 7.5 IPA (Isopropyl Alcohol) 37 / 11 Hydrogen* 39 / 12 Methane* 43 / 13 LPG* 43 / 13 Polypropylene Pellets 33 / 10 Silane** 22 / 7 Office Paper 20 / 6 |
Response Time | Typically 3 seconds |
Adjustable Time Delay | Up to 30 seconds |
Sensitivity Ranges | 1 ft2 (0.1m2) n-heptane pan fire from 50 ft (15m) |
Field of View | Horizontal 100º; Vertical 95º |
Built-in-Test (BIT) | Automatic (and Manual) |
Temperature Range | Operating: -67ºF to +167ºF (-55ºC to +75ºC) Option: -67ºF to +185ºF (-55ºC to +85ºC) Storage: -67ºF to +185ºF (-55ºC to +85ºC) |
Humidity | Up to 95% non-condensing (withstands up to 100% RH for short periods) |
Heated Optics | To eliminate condensation and icing on the window |
Hazardous Area Ex Approvals: ATEX approval remark , IECEx approval remark , FM approval remark , CSA approval remark , CU TR approval remark , CIMFR approval remark
Functional Approvals: FM approval remark , EN54-10 approval remark , CPD approval remark
Reliability Approvals: SIL2 approval remark
Other Approvals: CAL FIRE approval remark , AFP approval remark
Spectrex 40/40U-UB UV Flame Detector - Data Sheet 166.4 KB |