Multiple parameter meter that simultaneously measures and records CO2, humidity and temperature
Range of application | 0…50 °C / 0…100 %RH, non-condensing |
Accuracy at 23 ±5 °C | ±30 ppm ±5 % of the measured value, <2.5 %RH (10...90 %RH), ±0.3 °K |
Measuring range | 0...5000ppm; 0...100%RH; -20...60°C |
Measurement principle | Non dispersive infrared (NDIR) with automatic baseline correction (ABC) |
Adjustment points | Automatic calibration, manual calibration at 400 ppm and 35, 80 %RH |
Pressure dependency | +1.6 % reading per kPa |
Zero drift | <10 ppm/year |
Power supply / Power consumption | Via AC1214 AC adapter (included in the delivery package) |
Current consumption | 50 mA |
Measured value memory | 40,000 values with time stamp, automatic recording (%RH / °C / CO2 / external temperature probe) |
Warm-up time | <1 min. |
Long-term stability | < 1.5 %RH per year |
Humidity sensor | ROTRONIC HYGROMER® IN-1 |
Temperature sensor | Thermistor |
Response time | <10 sec @ 30 cc/min. flow, <3 min diffusion time |
Response time t 63 | <30 s, without filter |
Parameters shown | CO2, relative humidity and temperature |
Alarm indicators | Adjustable for CO2 measurement |
Real time clock w.backup battery | Yes |
Exploitation software | ROTRONIC SW21 free of charge, HW4 subject to charge |
Housing | ABS |
IP protection rating | IP30 |
Maintenance | No maintenance (standard indoor application) |
Dimensions | 157 x 120 x 45 mm |
Weight | Approx. 200 g |
Rotronic CL11 Indoor Air Quality Data Logger - Data Sheet 728.4 KB |