Available with single or duplex receptacles, in 16 or 30 amps with a variety of voltages, and pin configurations
Designed specifically for hazardous (classified) location clean rooms, such as found in the pharmaceutical industry, where equipment must be easy to clean and free of contaminant holding cavities. Electrical devices should also be flush wall mounted with concealed wiring, to minimize contamination.
• Available with single or duplex receptacles, in 16 or 30 amps with a variety of voltages, and pin configurations.
• Color coding and pin configuration makes it physically impossible to mate plugs and receptacles of different voltages and current ratings (per IEC 60 309-2).
• Flush mounting, smooth contours for easy cleaning.
• Enclosure made of 316L stainless steel with concealed gasket.
• Interlocked switch mechanism prevents accidental removal of plug from receptacle under load.
• The internal disconnect switch includes an auxiliary contact for indicating control circuits.
NEC & CEC | Class I, Division 2, Groups A,B,C,D Class I, Zone 2, Group IIC T6 Enclosure Type 3 & 3R |
ATEX | II 2G Ex de IIC T5/T6, IP65 PTB 01 ATEX 1001 |
R. Stahl CRP 8125/5 Series Clean Room Receptacle Panels - Data Sheet 1.2 MB |