Bipolar Isolated DIN Rail Signal Conditioner for Process Signals
The DRSL-DC4 bipolar isolated DIN rail signal conditioner provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. The DRSL-DC4 can be used for signal conversion of standard bipolar analog process signals into unipolar analog signals. The unit offers isolation between input, output and supply, provides surge suppression and protects control systems from transients and noise.
Input | |
Current Input | |
Programmable Measurement Ranges | ±10 mA, ±20 mA |
Functional Range, Current Input | -23 to 23 mA |
Input Voltage Drop | <1V @ 23 mA |
Voltage Input | |
Programmable Ranges | ±5V, ±10V |
Functional Range | -11.5 to 11.5V |
Input Resistance | ≥1 MΩ |
Output | |
Current Output | |
Programmable Signal Ranges | 0 to 20 mA, 4 to 20 mA |
Functional Range | 0 to 23 mA |
Load | 23 mA/600 Ω max (per channel) |
Load Stability | ≤0.002% of span/100 Ω |
Current Limit | ≤28 mA |
Voltage Output | |
Programmable Signal Ranges | 0 to 10V, 2 to 10V, 0 to 5V, 1 to 5V |
Functional Range | 0 to 11.5V |
Load | >10 kΩ min |
General | |
Supply Voltage (via Power Rail or Connectors) | 16.8 to 31.2 Vdc |
Power Consumption | 0.8 W max |
Internal Consumption | 0.4 W typical/0.65 W max |
Isolation | Input/output/supply |
Isolation Voltage (Test) | 2.5 kVac |
Isolation Voltage (Working) | 300 Vac |
MTBF | >241 years, according to IEC 61709 (SN29500) |
Signal/Noise Ratio | >60 dB |
Cut-Off Frequency (3 dB) | >100 Hz or 10 Hz (selectable via DIP-switch) |
Response Time (0 to 90%, 100 to 10%) | <7 ms or <44 ms |
Span | Corresponds to presently selected DIP switch output range Accuracy: <±0.05% of span |
Temperature Coefficient | <±0.01% of span/°C |
EMC Immunity Influence | <±0.5% of span |
Extended EMC Immunity | |
NAMUR NE 21, A Criterion, Burst | <±1% of span |
Environmental | |
Operating Temperature | -25 to 70°C (-13 to 158°F) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Calibration Temperature | 20 to 28°C (68 to 82°F) |
Relative Humidity | 0 to 95% RH non-condensing |
Protection Degree | IP20 |
Installation Area | Pollution degree 2 and measurement/overvoltage category II |
Mechanical | |
Dimensions | 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5") |
Weight | 70 g (0.15 lb) approx |
DIN Rail Type | DIN EN 60715 - 35 mm |
Wire Size | 0.13 x 2.5 mm²/AWG 26 to 12 stranded wire |
Screw Terminal Torques | 0.5 Nm |
OMEGA DRSL-DC4 DIN Rail Signal Conditioner for Bipolar Process Inputs - Data sheet 550.4 KB |