` DRSL-DC4 DIN Rail Signal Conditioner for Bipolar Process Inputs

OMEGA

DRSL-DC4 DIN Rail Signal Conditioner for Bipolar Process...

Bipolar Isolated DIN Rail Signal Conditioner for Process Signals

Call Today!
800-567-8686 Normally ships in 2-3 Weeks

  Request Quote

Can We Help You?

CALL US   EMAIL US   CHAT LIVE

Our product experts are here to help you find the right solution for your application!

 The DRSL-DC4 bipolar isolated DIN rail signal conditioner provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. The DRSL-DC4 can be used for signal conversion of standard bipolar analog process signals into unipolar analog signals. The unit offers isolation between input, output and supply, provides surge suppression and protects control systems from transients and noise.

 
The DRSL-DC4 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).
 

• Isolation and Conversion of Bipolar Process Voltage and Current Signals to Unipolar Signals
• Slimline Housing—Only 6 mm (0.24') Wide
• Multiple Signal Ranges (DIP-Switch Selectable)
• High Accuracy, <0.05% of Selected Rang

Input
Current Input
Programmable Measurement Ranges ±10 mA, ±20 mA
Functional Range, Current Input -23 to 23 mA
Input Voltage Drop <1V @ 23 mA
Voltage Input
Programmable Ranges ±5V, ±10V
Functional Range -11.5 to 11.5V
Input Resistance ≥1 MΩ
Output
Current Output
Programmable Signal Ranges 0 to 20 mA, 4 to 20 mA
Functional Range 0 to 23 mA
Load 23 mA/600 Ω max (per channel)
Load Stability ≤0.002% of span/100 Ω
Current Limit ≤28 mA
Voltage Output
Programmable Signal Ranges 0 to 10V, 2 to 10V, 0 to 5V, 1 to 5V
Functional Range 0 to 11.5V
Load >10 kΩ min
General
Supply Voltage (via Power Rail or Connectors) 16.8 to 31.2 Vdc
Power Consumption 0.8 W max
Internal Consumption 0.4 W typical/0.65 W max
Isolation Input/output/supply
Isolation Voltage (Test) 2.5 kVac
Isolation Voltage (Working) 300 Vac
MTBF >241 years, according to IEC 61709 (SN29500)
Signal/Noise Ratio >60 dB
Cut-Off Frequency (3 dB) >100 Hz or 10 Hz (selectable via DIP-switch)
Response Time (0 to 90%, 100 to 10%) <7 ms or <44 ms
Span Corresponds to presently selected DIP switch output range
Accuracy: <±0.05% of span
Temperature Coefficient <±0.01% of span/°C
EMC Immunity Influence <±0.5% of span
Extended EMC Immunity
NAMUR NE 21, A Criterion, Burst <±1% of span
Environmental
Operating Temperature -25 to 70°C (-13 to 158°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Calibration Temperature 20 to 28°C (68 to 82°F)
Relative Humidity 0 to 95% RH non-condensing
Protection Degree IP20
Installation Area Pollution degree 2 and measurement/overvoltage category II
Mechanical
Dimensions 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight 70 g (0.15 lb) approx
DIN Rail Type DIN EN 60715 - 35 mm
Wire Size 0.13 x 2.5 mm²/AWG 26 to 12 stranded wire
Screw Terminal Torques 0.5 Nm
Item
Description
Availability
Price
Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length
Normally ships in 2-3 Weeks
Call Today!
800-567-8686
Power connector unit, 24 Vdc/2.5 A output to power rail
Normally ships in 3-4 Weeks
Call Today!
800-567-8686
Module stop (screwed onto DIN rail to support and hold mounted devices)
Normally ships in 2-3 Weeks
Call Today!
800-567-8686


Your Recently Viewed Items...