` DRSL-TC-ISO DIN Rail Thermocouple Input Signal Conditioners

OMEGA

DRSL-TC-ISO DIN Rail Thermocouple Input Signal Condition...

Thermocouple Input DIN Rail Signal Conditioners

Call Today!
800-567-8686 Normally ships in 2-3 Weeks

  Request Quote

Can We Help You?

CALL US   EMAIL US   CHAT LIVE

Our product experts are here to help you find the right solution for your application!

 The DRSL-TC Series thermocouple input DIN rail signal conditioners provide a competitive choice in terms of both price and technology for interfacing thermocouple inputs to SCADA systems or PLC equipment.

 
The DRSL-TC and DRSL-TC-ISO can be used for signal conversion of standard Type J or K thermocouple inputs into unipolar analog signals.
 
The DRSL-TC-ISO isolated model offers 3-way isolation between input, output and supply and provides surge suppression and protects control systems from transients and noise. Low power consumption facilitates DIN rail mounting without the need for any air gap. Easy configuration of more than 1000 factory calibrated measurement ranges is done via DIP-switches. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

• DRSL-TC Non-Isolated and DRSL-TC-ISO Isolated Models
• Accepts Type J and Type K Thermocouples
• Pre-Calibrated Temperature Ranges Selectable via Dip-Switches
• Slimline Housing—Only 6 mm (0.24') Wide

Input
Type J or K thermocouple
Temperature Range
Type J -100 to 1200°C (-148 to 2192°F)
Type K -180 to 1372°C (-292 to 2501°F)
Sensor and Cable Specifications 5 kΩ per wire
Cold Junction Compensation (CJC) Internal or external (selectable)
CJC Accuracy via External CJC (Pt100 RTD Sensor) Better than ±0.15°C (DRSL-TC-ISO only)
CJC via Internally Mounted Sensor Better than ±2.5°C
Open Thermocouple Detection (DIP switch selectable upscale or downscale)
Output
Current Output
Programmable Signal Ranges 0 to 20 and 4 to 20 mA
Range Limits (NAMUR NE43 Out of Range) Below 3.8 mA or above 20.5 mA for 4 to 20 mA output; 0 mA or above 20.5 mA for 0 to 20 mA output
Sensor Error Detection (DIP Switch Selectable for Enable or None) Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output
Incorrect DIP-Switch Setting Indentification 0 mA
Output Error Level DIP switch selectable for upscale or downscale
Load 21 mA/600 Ω /12.6V max
Load Stability ≤0.01% of span/100 Ω
Voltage Output
Programmable Signal Ranges 0 to 10V, 2 to 10V, 0 to 5V and 1 to 5V
Range Limits (Out of Range) Range ±2.5%
Incorrect DIP Switch Setting Identification 0V
Load >10 kΩ min
General
Supply Voltage
DRSL-TC 16.8 to 31.2 Vdc via connectors
DRSL-TC-ISO 16.8 to 31.2 Vdc via power rail or connectors
Power Consumption 0.7 W max
Internal Consumption 0.65 W max
Isolation (DRSL-TC-ISO Only) Input/output/supply
Isolation Voltage, Test (DRSL-TC-ISO Only): 2.5 kVac (reinforced)
Isolation Voltage, Working (DRSL-TC-ISO Only) 300 Vac
Status LED Green LED indicates operational status of the unit and input sensor
Normal Operation Flashes for 15 ms at 13 Hz rate
Sensor Error Flashes for 15 ms at 1 Hz rate
Incorrect DIP Switch Setting Flashes for 500 ms at 1 Hz rate
Hardware Failure LED off
Signal/Noise Ratio >60 dB
Response Time (0 to 90%, 100 to 10%) <30 ms/300 ms (selectable, provides either fast response or signal dampening as needed)
Accuracy
DRSL-TC Better than 1.0°C or ±0.1% of selected input range
DRSL-TC-ISO Better than 0.5°C or ±0.05% of selected input range
Temperature Coefficient ≤±0.1°C/°C or ≤±0.01%/°C
EMC Immunity Influence <±0.5% of span
Extended EMC Immunity NAMUR NE 21, A Criterion, Burtst <±1% of span (span = selected input range)
Environmental
Operating Temperature -25 to 70°C (-13 to 158°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Calibration Temperature 20 to 28°C (68 to 82°F)
Relative Humidity 0 to 95% RH non-condensing
Protection Degree IP20
Installation Area Pollution degree 2 and measurement/overvoltage category II
Mechanical
Dimensions 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight 70 g (0.15 lb) approx
DIN Rail Type DIN EN 60715 - 35 mm
Wire Size 0.13 x 2.5 mm²/ AWG 26 to 12 stranded wire
Screw Terminal Torque 0.5 Nm
Item
Description
Availability
Price
Module stop (screwed onto DIN rail to support and hold mounted devices)
Normally ships in 2-3 Weeks
Call Today!
800-567-8686
Power connector unit, 24 Vdc/2.5 A output to power rail
Normally ships in 3-4 Weeks
Call Today!
800-567-8686
Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length
Normally ships in 2-3 Weeks
Call Today!
800-567-8686


Your Recently Viewed Items...