Explosion protected lights with auto-testing emergency ballast
The EXLUX 6008 Series carries out pre-programmed testing schedules, monitors emergency ballast performance and battery charging. In case of power failure the Autotesting Emergency Ballast automatically switches to emergency mode, keeping one lamp illuminated at reduced lumen output for a minimum of 90 minutes. When AC power is restored, the luminaire returns to AC supply. The EXLUX 6008 Series of Emergency Luminaires are designed for hostile and hazardous locations where reliability and rugged performance are critical. The housing is constructed of fiberglass reinforced polyester (FRP) with a single piece, low glare polycarbonate lens. They are supplied with flameproof electronic ballasts as standard, which are designed to edition 4 of IEC 60079-7 Annex H for control of the “End of Life” of the lamps. The luminaires also come with a cover interlock switch which automatically de-energizes the luminaires when opening for relamping.
NEC & CEC | Class I, Zone 1 & 2, AEx dem IIC T4 Class I, Division 2, Groups A,B,C,D, T4 Class II, Divisions 1 & 2, Groups E,F,G Class III Types 3, 4, 4X & IP66 File No. J.I.3D2A9.AE |
Supply Voltage | 120V, 50-60Hz |
Ambient Temperature Range | AC & Battery Operation +50°C (+122°F)Max. –20°C (–4°F) Min. Charging & Test Operation +50°C (+122°F) Max. –5°C (+23°F) MIN. |
R. Stahl EXLUX 6008 Series Fluorescent Emergency Luminaires - Data Sheet 199.5 KB |
R. Stahl EXLUX 6008 Series Fluorescent Emergency Luminaires - Dimensions 131.3 KB |