Monitor and control up to 3 spaces, monitoring up to 6 parameters for each room
Dimensions | 9.25” W x 6.3” H x 0.65”D (215.0mm x 160.0mm x 16.51mm) |
Mounting | Triple-gang, double deep electrical box. RACO 697, Appleton M3-350, or equivalent |
Case | Fire-retardant plastic UL94 V-0 |
Weight | 2 lbs |
Display | 7” Projected Capacitive (PCAP) multitouch. 800 x 480 pixels. Usable with medical gloves. |
Display Brightness | 1-7 |
USB Port | Micro-USB port for configuration cloning between units and software upgrades. |
Audible Alarm | Dual piezo with 3 volume levels (0-75 dB max.) |
Protocols | BACnet/IP using IPv4, Ethernet CAT5 cables with RJ45 BACnet MS/TP up to 76.8 kbps, 3-conductor, twisted, shielded 16-24 AWG cable |
Power | 24 VAC (18-32 VAC operational), 50-60 HZ |
Power Draw | 13 W max, 10 W typical |
Wire | 2 or 3-conductor (depending on application) stranded unshielded twisted pair, 16-24 AWG |
Connections | Removable Terminal Blocks |
Operating Temp. °F (°C) | 32 to 120 (0 to 50) |
Storage Temp. °F (°C) | -40 to 185 (-40 to 85) |
Operating Humidity | 5 to 95% RH (non-condensing) |
Ingress Protection (IP) Rating | IP54 |
Chemical Resistance | Exposed surfaces are chemically resistant to vaporized hydrogen peroxide (VHP), formaldehyde, chlorine dioxide (clidox), perchloric acid, sodium hypochlorite 3-6% (bleach), quaternary ammonium 7% in 1:128 tap water (ammonia). |
Accuracy RSS | ±0.25% |
Non-Linearity (BFSL) | ±0.24% |
Hysteresis | ±0.05% |
Non-Repeatability | ±0.05% |
Span Setting Tol. | ±0.5% Rdg |
Zero/Span Shift % FS | ± 0.03% PSI (±0.05% FS) |
Overpressure | ±1 PSI (15” WC for ≤0.10” WC FS) |
Pressure Media | Air or non-conductive, non-explosive gases |
Pressure Fittings | 3/16” barbed fittings |
Altitude | 6562 ft. (2000 m) max. |
Position | Housing to be 90° in reference to level surface, ±5° |
View All Part Numbers