Measures relative humidity, temperature and dew/ frost point in indoor environments and has freely scalable voltage and current outputs
The Probe can cover a wide voltage supply range and the freely selectable output signals can be used for a wide range of applications without adjustments. The XD OEM is available in different configurations (0…1/5/10 V) and has extensive settings and functions that can be configured and enabled with the ROTRONIC HygroSoft software after connecting to a PC.
Humidity Sensor | ROTRONIC HYGROMER® HT-1 |
Temperature Sensor | PT100 1/3 Class B |
Accuracy at 23°C | ±0.8 %rh / 0.2 K |
Resolution AirChip3000 | ˂0.02 %rh /0.01 K |
Long-Term Long-term Stability Humidity Sensor | <1 % rH / year |
Probe Measurement Range | -40…85 °C / 0…100%rh non-condensing |
Electronics Operating Range | -40…85 °C / 0…100%rh non-condensing |
Output signals (analog) | Freely scalable 0…1/5/10 V 0(4)…20mA |
Output Signals (digital) | UART or RS-485 |
Accuracy at 23°C Output signal | ˂1 mV(1 V) / <10mV(10V) / ˂20 uA |
Calculation | Dew point or frost point, freely scalable |
Power Supply | 5…16 VAC / 5…24 VDC (0…1 V) 12…16 VAC / 16…24 VDC (all Outputs) |
Current consumption | 7 mA (typical) @ 24VDC, 0…10 V 12 mA (typical) @ 5VDC, 0…1 V |
Humidity Adjustment | 1-point or multi-point humidity adjustment / calibration |
Temperature Adjustment | 1-point or multi-point temperature adjustment / calibration |
Housing | Polycarbonate |
Filter | Polyethylene, 40 um |
IP Protection & Fire Protection Class | IP65 / Corresponds to UL94-HB |
Dimension | Ø 15mm x 140 mm |
View All Part Numbers