Precision Digital

PD6600 Loop Leader Loop-Powered Process Meter

General-purpose, 1/8 DIN, loop-powered process meter with 4 front panel buttons and a dual line display (5 digit top line and 8 digit bottom line)

Starting At
$275.00 CAD
SKUs available for immediate delivery!
See our 'In Stock' list below!

Configure   Request Quote

Can We Help You?

CALL US   EMAIL US   CHAT LIVE

Our product experts are here to help you find the right solution for your application!

The Loop Leader PD6600 is a general-purpose, loop-powered, 1/8 DIN process meter. The four front panel buttons make setup and programming of the meter simple and intuitive. A dual-line display featuring five digits on the top line and eight digits on the bottom line, preprogrammed engineering units, and optional bargraph display (PD6604) or feet and inches display (PD6603) provide a clear and attractive presentation of the process. The units of measure can be changed as needed within a unit class (e.g. volume, temperature, pressure) without the need to re-scale the meter.

The dual-line display can be customized by the user to operate in such a way as to satisfy a specific application. Typically, the top line is used for the process variable while the bottom line is used for engineering units, custom tag, or process variable percentage of full scale. Three programmable function keys and a digital input come standard and allow the meter to be customized for use in specialized applications.

All models come equipped with two open collector outputs and are available with two solid state relays and a 4-20 mA analog output. These outputs can be programmed for alarm indication, signal retransmission via pulse or analog signal, pump control, and a number of other useful features.

The fact that this meter is loop-powered means that there is no need to run additional, costly power lines; the meter gets all of the power it needs from the 4-20 mA loop. The Loop Leader loop-powered process meter is built in a shallow-depth case with a NEMA 4X/IP65 front and features loop-powered backlighting and a wide -40 to 167°F (-40 to 75°C) operating temperature range. It doesn't matter if it's indoors or outdoors, in bright sunlight or a dimly lit plant, or in an area that is wet, dirty, hot, or cold, the Loop Leader can go just about anywhere.

     


 

• Loop-Powered Backlight with Red Backlight for Alarm Conditions
• Loop-Powered Process Meter
• 1.5 Volt Drop (4.5 Volt Drop w/ Backlight)
• NEMA 4X, IP65 Front
• -40 to 167°F (-40 to 75°C) Operating Temperature Range
• Five Digit Top Line
• Alphanumeric tag names
• Dual Line Display
• 1/8 DIN Shallow Depth Case
• Optional Loop-Powered Solid State Relays
• Optional 4-20 mA Analog Output
• Open Collector Output Standard
• Optional Bargraph Display (PD6604)
• Timer functions for open collectors and relays
• Relay pump alternation based on level and time
• Relay runtime and cycle count
• Multi-Point Linearization, Square Root, Programmable Exponent, and Round Horizontal Tank Input Conditioning Functions
• Automatic units conversion for volume, height, temperature, pressure, weight, and rate

Display Top: 0.7” (17.8 mm), Bottom: 0.4” (10.2 mm); 14-segment alphanumeric

PD6602 & PD6604: Top: 5 digits -9999 to 99999

PD6603: Top: 5 digits -99 ft. 11 in. 15/16 to 999 ft. 11 in. 15/16

Bottom: 8 digits -9,999,999 to 99,999,999

Bottom line separated by commas
Display Update Rate Ambient > -10°C: 1 Update/Second

Ambient > -20°C: 1 Update/2 Seconds

Ambient -40°C: 1 Update/10 Seconds
Over Range PD6602 & PD6604: Top: 99999; Bottom: 99,999,999 (flashing)

PD6603: Top: 999 ft. 11 15/16 in.; Bottom: 99,999,999 (flashing)
Under Range PD6602 & PD6604: Top: -9999; Bottom: -9,999,999 (flashing)

PD6603: Top: -99 ft. 11 15/16 in.; Bottom: -9,999,999 (flashing)
Programming Method Front panel
Noise Filter 1, 2, 4, 8, 16 sec.
Noise Filter Bypass 0.1 to 99.9% FS
Recalibration Recalibration is recommended at least every 12 months.
Max/Min Display Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
Password Programmable password restricts modification of programmed settings.
Non-Volatile Memory All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Normal Mode Rejection 64 dB at 50/60 Hz
Environmental Operating temperature range: -40 to 75°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
Connections Removable screw terminals accept 12 to 22 AWG wire
DI Digital Input Contacts 2.1 VDC on contact. Connect normally open contacts across DI+ to DI-
DI Digital Input Logic Levels Logic High: 2.4 to 30 VDC (max)

Logic Low: 0 to 0.9 VDC
Enclosure & Materials 1/8 DIN, high impact plastic, NORYL® Polyphenylene Ether & Polystyrene blend (PPE PS) Resin, UL 94V-0, color: gray

Gasket: Silicone Rubber

Faceplate: LEXAN® Polycarbonate (PC) Film

Buttons: Silicone rubber; Color: black
Mounting 1/8 DIN panel cutout required. Two panel mounting bracket assemblies provided
Tightening Torque Screw terminal connectors: 4.5 lb-in (0.5 Nm)
Mounting screws: 8.0 lb-in max. (0.9 Nm)
Overall Dimensions (W x H x D) 4.68" x 2.45" x 3.79" (119 mm x 62 mm x 96 mm)
Weight 8.7 oz (247g) w/ option board
Warranty 3 years parts and labor
SKU
Quantity
Price
PD6602-LNN
2
CAD