The ProtEX PD6830X is an explosion-proof, RS485 serial input Modbus® RTU scanner capable of scanning up to 16 Modbus variables and displaying them on an easy-to-read, dual-line, LCD display. This Modbus scanner can be programmed as a Modbus RTU master, slave, or snooper. The PD6830X is available in two upper display line configurations: 5-digit decimal display and feet & inches display with bar graph. The lower line is the same for both versions and consists of seven alphanumeric characters. Like all ProtEX products, the PD6830 carries FM, CSA, ATEX, and IECEx approvals for use in hazardous areas. Two features that really make the PD6830X stand out are its wide viewing angle display and SafeTouch® through-glass buttons. These buttons allow the PD6830X to be programmed and operated through the glass, thus eliminating the need to remove the cover in a hazardous area.

               

• Modbus® Master, Slave, or Snooper Mode
• Scan up to 16 Modbus Process Variables
• 5-Digit Decimal or Feet & Inches Level Display
• On-Board Three-Wire RS-485 with Modbus
• Independent Scaling, Tag, and Unit for Each PV
• 7 Alphanumeric Character 0.4" (10.2 mm) Lower Display for Process Variables, Custom Units, and Tags
• Explosion-Proof, IP68, NEMA 4X Enclosure
• SafeTouch® Through-Glass Button Programming
• Isolated 4-20 mA Output Option
• Pulse Input for Rate, Total, and Grand Total
• 13-Digit Totalizer with Total Overflow Feature
• Password Protection
• Backlight Standard on All Models
• Automatic Rate, Total, and Grand Total Unit Conversions
• Operates from -40 to 75°C
• Data Logging Functions and Modbus Accessible Data
• Two Isolated Pulse Outputs Standard, Up to 5 kHz

Decimal Display Top:Top Display: Five Digits (0 to 99999), 0.7" (17.8 mm) high, 7-segment, automatic lead zero blanking.
Bottom Display: Seven Characters, 0.4" (10.2 mm) high, 14-segment, automatic lead zero blanking.
Symbols: Total, grand total, high alarm, low alarm, SafeTouch button sleep mode/disable, password lock.
Feet & Inches Display Top Display: 0.60" (15.2 mm) high, 0 to 399FT, 1115/16 IN, 7-segment, programmable 1/16 or 1/8 fraction display.
Bottom Display: Seven Characters, 0.4" (10.2 mm) high, 14-segment, 7-digits.
Tank Level Indicator : 20-segments, F (Full) and E (Empty).
Alarm Indication: High and low alarm
Backlight: White
Display Assignment Top and Bottom Display*: Process Variables (PV); Alternating PV and Units, Tag and PV, or Tag, PV, and Units; Pulse Input Rate, Total, or Grand Total with Alternating Tag.
Bottom Display: All Top Display Options or Off
Units and tag independent for each PV, pulse input rate, total, and grand total.
*Note: On feet and inches display models, top display used only for level Modbus process variables or math channels.
Backlight White LED, 10 sec auto-off when battery powered. Backlight deactivated below temperature ≈ -20C
Alarm Indication Flashing display plus HI/LO (alarm) or SET indicators.
Scan and Update Rate Ambient > -20C: Modbus PV scan rate programmable from 2 to 99 seconds per PV. Tag and units programmable for 1 to 5 second alternation. Pulse input variables update 1/second. Rate update is dependent on gate settings.
Ambient < -20C: All Modbus scan, alternating units and tags, and pulse input variables update/10 seconds minimum.
Over Range Upper Display: Decimal display flashes 99999
Level display flashes to 399FT 1115/16 IN
Lower Display: Flashes 9999999
Under Range Upper Display: Decimal display flashes -9999
Level display flashes to 399FT 1115/16 IN
Lower Display: Flashes -999999
Programming Method Four SafeTouch through-glass buttons when cover is installed. Four internal push buttons when cover is removed.
Recalibration Calibrated at the factory to read frequency in Hz. No recalibration required.
Password Menu Options Three programmable password selections can be used for the following: restrict modification of settings, prevent resetting the total or grand total without the password, or permanently lock out the ability to change or reset the grand total or any grand total related settings(making a non-resettable grand total).
Pass: Restricts modifications of programmed settings to require re-entering the password to make changes.
Pass T: Restricts the reset of total to require re-entering the password. Disables the manual mode reset contact.
Pass GT: Restricts the reset of grand total to require re-entering the password. May enable a non-resettable grand total and permanent lockout of grand total-related settings with a specific password
Input Power 9-30 VDC, 38 mA max. 2.2 W
Data Logging Up to 512 records, recorded 4/day at specific times or at defined time intervals. Record contains first eight enabled Modbus PVs; C1-4 if enabled; date; time; pulse rate, total, and grand total with units; and log number.
Isolation All Models: 500 V opto-isolated pulse input-to-power/OC output with isolated input enabled, 500 V input/power-to-RS-485 serial communications. AXA Models: 500 V input/power-to-analog output.
Environmental Operating temperature range: -40 to 75C; Storage temperature range: -40 to 75C; Backlight deactivated below temperatures ≈ -20C; Relative humidity: 0 to 90% non-condensing
Non-Volatile Memory All programmed settings and total reading are stored in non-volatile memory for a minimum of ten years if power is lost.
Connections Screw terminals accept 12 to 22 AWG wire
Enclosure Explosion-proof die-cast aluminum with glass window, corrosion resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Copper-free (0.3%). Default conduit connections: Three " NPT threaded conduit openings. One " NPT metal plug with 12 mm hex key fitting installed. Additional conduit opening configurations and plugs may be available; verify quantity and sizes on specific device labeling during installation.
Mounting May be mounted directly to conduit. Two slotted flanges for wall mounting or NPS 1" to 2" or DN 40 to 65 mm pipe mounting.
Display Orientation Display may be mounted at 90 increments up to 270 from default orientation.
Overall Dimensions (W x H x D) 5.67" x 5.24" x 4.88" (144 mm x 133 mm x 124 mm)
Weight 5.00 lbs (80 oz, 2.27 kg)
Warranty 3 years parts and labor

Item
Description
Availability
Price
PDA0001 Reducer for the PD68XX
3/4" M-NPT to F-M20 Reducer for the PD68XX
Normally ships in 1-2 Weeks
$33.75 CAD
PDA0002 Reducer for the PD68XX
3/4" M-NPT to 1/2" F-NPT Approved Reducer for the PD68XX
Normally ships in 1-2 Weeks
$33.75 CAD
PDA6846 Pipe Mounting Kit
Pipe mounting kit for ProtEX
Normally ships in 1-2 Weeks
Starting At
$13.50 CAD
Configure
PDA8068 Serial Adapter
USB Serial Adapter for PD6830 & PD6730
Normally ships in 1-2 Weeks
$110.70 CAD
PDABAT36C Approved Replacement Battery
Approved replacement 3.6 V C-Cell lithium battery
Normally ships in 1-2 Weeks
$60.75 CAD
PDABAT36D Replacement Battery
Approved replacement 3.6 V d-cell lithium battery
Normally ships in 1-2 Weeks
$81.00 CAD
PDAPLUG75 Stopping Plug
3/4" NPT 316 stainless steel stopping plug with approvals
Normally ships in 1-2 Weeks
$27.00 CAD


Chat Live