Skip to main content
Press Enter
Spectrex Inc.

SafEye Quasar 900 Open Path Gas Detector

Provides continuous monitoring for combustible hydrocarbon gases, 7-200m detection range, built in event recorder

Have questions? We're here to help!
Have questions? We're here to help!

The SafEye Quasar 900 is an open path detection system which provides continuous monitoring for combustible hydrocarbon gases. It employs “spectral fingerprint” analysis of the atmosphere using the Differential Optical Absorption Spectroscopy (DOAS) technique.

 The Quasar 900 consists of a Xenon Flash infrared transmitter and infrared receiver, separated over a line of sight from 23 ft (7m) up to 660 ft (200m) in extremely harsh environments where dust, fog, rain, snow or vibration can cause a high reduction of signal.
 
The Quasar 900 transmitter and receiver are both housed in a rugged, stainless steel, ATEX and IECEx approved enclosure. The main enclosure is EExd flameproof with an integral, segregated, EExe increased safety terminal section.
 
The hand-held communication unit can be connected in-situ via the intrinsically safe approved data port for prognostic and diagnostic maintenance. The Quasar 900 is approved to FM/FMC per Class I Div 1 Group B, C and D and Class I, II Div 1 Group E, F and G, and ATEX/IECEx per Ex d e ib [ib Gb] IIB + H2 T4 Gb, Ex tb IIIC T135°C Db.

The Quasar 900 includes heated windows to eliminate condensation and icing, HART capability for digital communication and is designed to meet SIL2 per IEC61508 and FM performance approved per FM6325 and tested per EN60079-29-4.

• Detects Hydrocarbon gases including methane, ethylene, Propane, Ethane, Butane etc.
• Detection range: 7-200m in three different models (same detector different sources)
• Built in event recorder – real time record of the last 100 events
• Fast connection to Hand-Held for prognostic and diagnostic maintenance
• Heated optics
• SIL2 approved, per IEC61508
• Outputs:
  - 0-20mA
  - HART protocol for maintenance and asset managements
  - RS-485, Modbus Compatible
• High reliability – MTBF minimum 100,000 hours
• User programmable via HART or RS-485
• 3 years warranty (10 years for the flash source)
• Ex approval:
  - FM/FMC approved per - Class I Div 1 Group B, C and D; Class I, II Div 1 Group E, F and G
  - ATEX & IECEx approved per - Ex d e ib [ib Gb] IIB + H2 T4 Gb; Ex tb IIIC T135°C Db
  - Performance test: Approved to FM6325 and tested per EN60079-29-4 by FM

Detection RangeModel 901:
Feet 23-66
Meters 7-20

Model 902:
Feet 50-132
Meters 15-40

Model 903:
Feet 115-330
Meters 35-100

Model 904:
Feet 265-660
Meters 80-200
Detected GasC1-C8
Response Time3 sec.
Immunity to False AlarmNot influenced by solar radiation, hydrocarbon flames and other external IR radiation sources.
Sensitivity Range0-5 LEL.m methane and propane
0-8 LEL.m ethylene
Spectral Response2.0 - 3.0μm
Displacement/Misalignment Tolerance±0.5°
Drift±7.5% of the reading or ±4% of the full scale (whichever is greater)
Minimum Detectable Level0.15 LEL.m
Temperature Range–67°F (–55°C) to 149°F (65°C)
HumidityUp to 95% non-condensing (withstands up to 100% RH for short periods)
Heated OpticsTo eliminate condensation and icing on the window
WarrantySafety system – 3 years
Flash source bulb – 10 years

  • Thumbnail of document Data Sheet - SafEye Quasar 900 Open Path Gas Detector
    Download

    Data Sheet - SafEye Quasar 900 Open Path Gas Detector

    Download
  • Thumbnail of document Manual - SafEye Quasar 900 Open Path Gas Detector
    Download

    Manual - SafEye Quasar 900 Open Path Gas Detector

    Download

Request a Service Quote

Get a customized quote for calibration, validation, repair, or training services designed to keep your instruments accurate and compliant.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more