` SafEye Quasar 900 Open Path Gas Detector

Spectrex Inc.

SafEye Quasar 900 Open Path Gas Detector

Provides continuous monitoring for combustible hydrocarbon gases, 7-200m detection range, built in event recorder

Call Today!
800-567-8686 Normally ships in 1-2 Weeks

  Request Quote

Can We Help You?

CALL US   EMAIL US   CHAT LIVE

Our product experts are here to help you find the right solution for your application!

The SafEye Quasar 900 is an open path detection system which provides continuous monitoring for combustible hydrocarbon gases. It employs “spectral fingerprint” analysis of the atmosphere using the Differential Optical Absorption Spectroscopy (DOAS) technique.

 The Quasar 900 consists of a Xenon Flash infrared transmitter and infrared receiver, separated over a line of sight from 23 ft (7m) up to 660 ft (200m) in extremely harsh environments where dust, fog, rain, snow or vibration can cause a high reduction of signal.
 
The Quasar 900 transmitter and receiver are both housed in a rugged, stainless steel, ATEX and IECEx approved enclosure. The main enclosure is EExd flameproof with an integral, segregated, EExe increased safety terminal section.
 
The hand-held communication unit can be connected in-situ via the intrinsically safe approved data port for prognostic and diagnostic maintenance. The Quasar 900 is approved to FM/FMC per Class I Div 1 Group B, C and D and Class I, II Div 1 Group E, F and G, and ATEX/IECEx per Ex d e ib [ib Gb] IIB + H2 T4 Gb, Ex tb IIIC T135°C Db.

The Quasar 900 includes heated windows to eliminate condensation and icing, HART capability for digital communication and is designed to meet SIL2 per IEC61508 and FM performance approved per FM6325 and tested per EN60079-29-4.

• Detects Hydrocarbon gases including methane, ethylene, Propane, Ethane, Butane etc.
• Detection range: 7-200m in three different models (same detector different sources)
• Built in event recorder – real time record of the last 100 events
• Fast connection to Hand-Held for prognostic and diagnostic maintenance
• Heated optics
• SIL2 approved, per IEC61508
• Outputs:
  - 0-20mA
  - HART protocol for maintenance and asset managements
  - RS-485, Modbus Compatible
• High reliability – MTBF minimum 100,000 hours
• User programmable via HART or RS-485
• 3 years warranty (10 years for the flash source)
• Ex approval:
  - FM/FMC approved per - Class I Div 1 Group B, C and D; Class I, II Div 1 Group E, F and G
  - ATEX & IECEx approved per - Ex d e ib [ib Gb] IIB + H2 T4 Gb; Ex tb IIIC T135°C Db
  - Performance test: Approved to FM6325 and tested per EN60079-29-4 by FM

Detection Range Model 901:
Feet 23-66
Meters 7-20

Model 902:
Feet 50-132
Meters 15-40

Model 903:
Feet 115-330
Meters 35-100

Model 904:
Feet 265-660
Meters 80-200
Detected Gas C1-C8
Response Time 3 sec.
Immunity to False Alarm Not influenced by solar radiation, hydrocarbon flames and other external IR radiation sources.
Sensitivity Range 0-5 LEL.m methane and propane
0-8 LEL.m ethylene
Spectral Response 2.0 - 3.0μm
Displacement/Misalignment Tolerance ±0.5°
Drift ±7.5% of the reading or ±4% of the full scale (whichever is greater)
Minimum Detectable Level 0.15 LEL.m
Temperature Range –67°F (–55°C) to 149°F (65°C)
Humidity Up to 95% non-condensing (withstands up to 100% RH for short periods)
Heated Optics To eliminate condensation and icing on the window
Warranty Safety system – 3 years
Flash source bulb – 10 years

Hazardous Area Ex Approvals: ATEX approval remark , IECEx approval remark , FM approval remark , FMC approval remark , Inmetro approval remark , CU TR approval remark 

Functional Approvals: FM approval remark , FMC approval remark , SIL2 approval remark , Type Approval approval remark 

 