Linearized and isolated RTD and Thermocouple transmitters are part of the Series SC4000 Iso Verter® II Signal Conditioning Modules. These modules completely isolate the input from the output and from the ground. Compatible with industry standard 35 mm DIN Rail mount transmitters and isolators, these modules are easily applied in new or existing installations.
| Isolation | 1500 VAC RMS. |
| Linearity | 0.1% of full scale. |
| Drift | ±0.02%/°C typical, ±0.05%/°C maximum. |
| Power Supply | SC: 85 to 265 VDC/VAC 50 to 400 Hz; SCL: 12 to 24 VDC/VAC 50 to 400 Hz. |
| Output Loads | Current: 600 Ω maximum Voltage: 500 Ω minimum (20 mA maximum). |
| Input Characteristics | SC4380: Voltage: 1 MΩ impedance, Current: 10 Ω; SC4151: RTD search current < 500 µA; SC4130: 3 MΩ impedance. |
| Case Size | 0.866" W (22.5 mm) x 2.950" H (75.0 mm) 3 3.880" D (98.5 mm). |
| Mounting | Mounts on industry standard 35 mm DIN Rail (DIN EN50022-35). |
View All Part Numbers