Provides rapid indication of voltage levels, faster and safer than old-fashioned solenoid testers
Specifications | ||
Temperature | Operating | -10°C - 55°C (14°F - 131°F) |
Storage | -30°C - 60°C (-22°F - 140°F) | |
Relative Humidity | 0°C - 30°C (32°F - 86°F), 90% 30°C - 40°C (86°F - 104°F), 75% 40°C - 50°C (104°F - 122°F), 45% | |
Altitude | Operating | 2,000 m (approx. 6,561.6 ft) |
Storage | 10,000 m (approx. 32,808.4 ft) | |
Battery Type / Life | Two (2) AAA, 40 h typical | |
Shock / Vibration | Sinusoidal vibration per MIL-PRF-28800F for a Class 2 instrument | |
Safety | ISA-82.02.01 (IEC 61010-1 Mod) Second Edition, CAN/CSA-C22.2 No. 61010-1 Second Edition, IEC 6010 - 1 to 1000 V CAT III / 600 V CAT IV Compliance to NFPA 70E* | |
AC Bandwidth | 45 Hz - 66 Hz | |
Maximum Working Voltage | 1000 V AC/DC | |
Maximum Measurable Voltage | 600 V AC/DC | |
Duty Cycle | Indefinitely for voltages up to 240 V For voltages between 240 V and 600 V the duty cycle is 30 s on / 300 s off For voltages above 240 V the tester must connect to a voltage source only for a MAXIMUM or 30 s and then disconnect for a minimum of 300 s | |
Voltage Hazard LED | LEDs turn on at voltages > 39 V AC/DC +/- 35% | |
LED Voltage Indication Levels for Canadian Version | 12 V, 24 V, 48 V, 120 V, 208 V, 240 V, 347 V, 480 V, 600 V | |
LEDs | LEDs turn on between 90% and 100% of the indicated voltage on the LED, except for the 12 V LED which turns on between 50% and 100% | |
LCD Accuracy on T+ PRO Only | AC Voltage | +/- (3% rdg + 2 digits) |
DC Voltage | +/- (2% rdg + 2 digits) | |
Resistance | +/- (5% rdg + 3 digits) | |
LCD Resolution | 0.1 V for voltages < 50 V, 1 V for voltages ≥ 50 V 0.01 kΩ for resistance measurement (for T+PRO/CAN only) | |
GFCI Test Current | 100 V - 150 V @ 6 mA - 9 mA AC, 150 V - 240 V < 12 mA | |
Standard Input Test Current | < 5 mA | |
Size (H x W x L) | 3.3 cm x 5.46 cm x 19.3 cm (1.3 in x 2.15 in x 7.6 in) | |
Weight | 0.28 kg (9.9 oz) | |
*When used properly per Article 110.9 Use of Equipment (A) Test Instruments and Equipment.
View All Part Numbers