It provides 2 channels of configurable inputs, and supports multiple voltage, RTD, thermocouple inputs with auto reference junction compensation. If parallel connected to an external precise resistance, it accepts current signal input. Each channel has its own digital filtering and can adjust its filtering degree.
Input Type | |
Thermocouple | K, J, T, E, R, S, B, N WRe5-WRe26 |
RTD | Pt100, Cu50 |
Linear Voltage | 0 to 20 mV, 0 to 60 mV, 0 to 100 mV, 0 to 1V, 0.2 to 1V |
Instrument input Range | K(-50 to 1300°C), S(-50 to 1700°C), R(-50 to 1700°C), T(-200 to 350°C), E(0 to 1000°C), J(0 to 1200°C), B(0 to 1800°C), N(-50 to 1300°C), WRe5%WRe26(0 to 2300°C), Pt100(-200 to 900°C) |
Linear Input | -9990 to 30,000 units defined by user |
Retransmission Accuracy | 0.3% FS ±1 digit (including input and output error) |
Output Specification | Can be freely defined in the range of 0 to 22 mA with maximum output voltage ≥11V |
Temperature Drift | ≥0.015%FS/°C (including the temperature drift of input and output) |
Electromagnetic Compatibility (EMC) | ±4 KV/5 KHz according to IEC61000-4-4 (EFT); 4 KV according to IEC61000-4-5 |
Isolation Withstanding Voltage | Voltage between power, signal input and output terminals ≥2300 Vdc; |
Power Supply | 100 to 240 Vac, -15%, +10% /50 to 60 Hz; or 24VDC |
Power Consumption | ≥3W |
Operating Ambient | Temperature -10 to 60°C; humidity ≥90%RH |
View All Part Numbers