Skip to main content
Press Enter
Burns Engineering

200A/200B Direct & Variable Immersion Platinum RTDs

General purpose direct and variable immersion platinum RTDs, available with M12 connector (200A), -196°C to 500°C

Have questions? We're here to help!
Have questions? We're here to help!

A direct immersion style RTD that features a 1/2″ NPT process connection and 1/2″ NPT instrument connection. The 1/4″ diameter stem is standard with an optional 3/16″ diameter available. Pressure rated to 3000 psi. Available with ratings for use in hazardous atmospheres. Single element with 3 or 4 wire circuit or dual 3 wire sensing elements.

A direct immersion style RTD that features field adjustable immersion length via a 316 SS compression fitting with PTFE or SS ferrules. PTFE allows for readjustment of the immersion length. Add the HD04 connection head for a convenient and durable method of attaching your extension cable. Other heads and indicators can also be added.

Sensor type RTD (Pt100)
Temperature range -196 to 500 C (-320.8 to 932 F)
Sensor style Direct Immersion
Sheath diameter 0.25", 0.188"
Immersion depth Fixed
Process connection 200A: 1/2" NPT
200B: None
Head connection NPT
Spring loaded for thermowell No
Wire termination Head
Hazardous rating Optional
  • Thumbnail of document Data Sheet - 200A/200B Direct & Variable Immersion Platinum RTDs
    Download

    Data Sheet - 200A/200B Direct & Variable Immersion Platinum RTDs

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.