 The Series 2900 Current to Pressure Transducer delivers reliable high performance for the toughest applications in the most hazardous environments. Its NEMA 4X housing is designed and FM and CSA approved for both intrinsically safe and explosion-proof operation. This unit has advanced circuitry which includes electronic feedback control for superior vibration protection and highly accurate output. The 2900 is not position sensitive and the easily accessible zero and span adjustment make field calibration quick and easy. For ease of installation, this model has input and output ports on both the front and back. It is also not vibration sensitive, which makes the 2900 ideal for field mounting on a valve. These features coupled with the unit's compact size help make set-up and installation simple.

• Designed for Hazardous Environments
• Vibration Resistant
• Explosion-proof
• Weatherproof and Intrinsically Safe
CSA Ratings:Class I, Division 1, Groups B, C and D; Class I, Division 2, Groups A, B, C and D; Class II, Division 1, Groups E, F and G; Class II and III, Division 2, Groups F and G.
FM Ratings:Explosion-proof for Class I, Division 1, Groups B, C and D. T6, Dust Ignition-proof for Class I, Division 1, Groups E, F and G, T6; Intrinsically safe for Class I, II and III, Division 1, Groups C, D, E, F and G, T4 hazardous (classified) locations and intrinsically safe for Class I, Zone 0, Group IIB, T4 hazardous (classified) locations and suitable for Class I, Groups A, B, C, D, T4 and Class II and III, Division 2, Groups F and G, T6 hazardous (classified) locations.
Agency Approvals:CE, CSA, FM.
Weight:1.8 lb (0.82 kg).
Enclosure Rating:Weatherproof NEMA 4X (IP65), explosion-proof and intrinsically safe.
Enclosure:Chromate-treated aluminum with epoxy paint.
Output Capacity:4.5 scfm (2.1 l/s) at 25 psig (1.7 bar) supply; 12.0 scfm (5.7 l/s) at 100 psig (6.9 bar) supply.
Air Consumption:0.05 scfm (0.02 l/s) at midrange typical.
Electrical Connection:1/2" female NPT.
Pressure Connections:1/4" female NPT.
Temperature Limits:Operating: -40 to 160°F (-40 to 71°C); Storage: -40 to 200°F (-40 to 93°C).
Power Requirement:Loop powered.
Deadband:0.02% of span.
Repeatability:±0.1% of span.
Hysteresis:±0.1% of span.
Accuracy:±0.1% of span.
Output:3 to 15 psig (0.2 to 1.0 bar), 6 to 30 psig (0.4 to 2.1 bar).
Air Supply:Minimum: 5 psig (0.3 bar) above maximum output; Maximum: 100 psig (6.9 bar).
Input Signal:4-20 mA.
Service:Oil free, clean dry air filtered to 40 microns.

 • Controlling valve actuators, pneumatic valve positioners, air cylinders, clutches, brakes, dampers, louvers and pumps

 
  • Thumbnail of document Data Sheet - 2900 Current to Pressure Transducer
    Download

    Data Sheet - 2900 Current to Pressure Transducer

    Download
  • Thumbnail of document Manual - 2900 Current to Pressure Transducer
    Download

    Manual - 2900 Current to Pressure Transducer

    Download

Accessories

Request a Service Quote

Get a customized quote for calibration, validation, repair, or training services designed to keep your instruments accurate and compliant.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more