 Model CLS1 Capacitance Level Switch provides reliable point level measurement of solids, liquids and slurries in metallic or non-metallic tanks and vessels. Model CLS1 detects the presence or absence of material in contact with the probe by sensing a change in the capacitance. Electronics provide highly sensitive measurement detection (requires less than a 1 picofarad shift from ambient). State of the art technology ignores material build-up on the vessel sidewall or along the probe assembly. One time calibration is simple with a single multi-turn potentiometer. Red LED on housing indicates sensor status. Unit features an adjustable 1-30 second time delay and a 5 amp, SPDT fail-safe relay output. Model CLS1 can be mounted vertically or horizontally.

• Electronics provide highly sensitive measurement detection (requires less than a 1 picofarad shift from ambient)
• State of the art technology ignores material build-up on the vessel sidewall or along the probe assembly
• One time calibration is simple with a single multi-turn potentiometer
• Red LED on housing indicates sensor status
• Adjustable 1-30 second time delay and a 5 A, SPDT fail-safe relay output
• Added installation flexibility with vertically or horizontally mounting
Weight:2.0 lb (0.91 kg).
Time Delay:Adjustable 1 to 30 s.
Fail-Safe:Switch selectable, high/low.
Sensitivity:Adjustable to <1 pF.
Mounting Orientation:Vertical or horizontal.
Process Connection:1" male NPS.
Conduit Connection:3/4" female NPT.
Power Requirements:120 VAC, 1.5 VA.
Electrical Rating:5 A @ 250 VAC.
Switch Type:SPDT.
Enclosure Rating:NEMA 4X (IP56), PVC, dust tight, water resistant.
Temperature Limits:Process: -40 to 240°F (-40 to 116°C); Ambient: -40 to 185°F (-40 to 85°C).
Wetted Material:CPVC.
Service:Solids, liquids, or slurries.

 • High or low level detection in bins, silos, tanks, hoppers, chutes and other vessels where liquids, solids or slurries are stored.

 
  • Thumbnail of document Data Sheet - CLS1 Capacitance Level Switch
    Download

    Data Sheet - CLS1 Capacitance Level Switch

    Download
  • Thumbnail of document Manual - CLS1 Capacitance Level Switch
    Download

    Manual - CLS1 Capacitance Level Switch

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more