 The DMD4059 accepts an input from full Wheatstone strain bridge sensors, pressure transducers or load cells. It provides filtering, amplifies, and converts the millivolt input signal into the selected dc voltage or current output that is linear to the input. The 3-way 1200V isolation eliminates ground loops, common mode voltages and greatly reduces noise pick-up. Sense wire connections are available to give maximum accuracy. Input, output, excitation and zero offset are field configurable via external rotary and slide switches. Offsets of up to ±100% of span can be used to cancel sensor offsets or tare fixed loads. Features such as red and green LEDs vary in intensity to show input and output activity and an output test button helps with set-up and troubleshooting.

• Standard DIN Rail Mounting
• Non-Interactive Zero and Span
• Fast Setup - Over 100 I/O Ranges
• Removable Connectors
Output Linearity, Ripple and NoiseBetter than ±0.1% of span, <10 mV rms ripple and noise
Compliance, Drive @ 20 mA20V, 1000&937; drive; current output can be selectively wired for sink or source
Current0-2 mA to 0-25 mA
Bipolar Voltage (10 mA max)±5 or ±10 Vdc
Voltage ( 10 mA max)0-1 to 0-10 Vdc
Output Ranges
Zero Offset (Tare)±100% of span in 15% increments
Maximum Lead Wire Resistance10Ω with 350Ω @ 10 Vdc
Sense Lead CompensationBetter than ±0.01% per 1Ω change in leadwire resistance
Stability±0.01% per °C
Fine Adjustment±5% via multi-turn potentiometer
Maximum Output10 Vdc @ 120 mA
Excitation VoltageSwitch selectable 0 to 10 Vdc in 1V increments
Input Impedance200 kΩ typical
Maximum0 to 400 mV range, 40 mV/V sensitivity
Input Range (unipolar) Minimum0 to 5 mV range, 0.5 mV/V sensitivity
Dimensions22.5 W x 117 H x 122 mm D (0.89 x 4.62 x 4.81"), height includes connectors
ConnectionsFour 4-terminal removable connectors 14 AWG max wire size
Environmental ProtectionIP40
MountingMounts to standard 35 mm DIN rail
Power Consumption2 to 5 W depending upon number of load cells
Low Voltage "DC" Option9 to 30 Vdc or 10 to 32 Vac
Standard Power80 to 265 Vac, 50/60 Hz or 85 to 300 Vdc
Thermal StabilityBetter than ±0.02% of span per °C
Operating Temp Reange-10 to 60 °C (14 to 140 °F)
Isolation1200 Vrms min, 3-way isolation, power to input, power to output and input to output
Common Mode Rejection100 db min
Response Time70 ms typical
Function Test ButtonSets output to test level when pressed. Adjustable 0 to 100% of span via potentiometer. Factory default is approx 50% of span.
Output Zero and Span (Fine Adjustment)Multi-turn potentiometers to compensate for load and lead variations, ±15% of span adjustment range typical
  • Thumbnail of document Data Sheet - DMD4059-DC DIN Rail Conditioners Convert Bridge Inputs to mA or Voltage
    Download

    Data Sheet - DMD4059-DC DIN Rail Conditioners Convert Bridge Inputs to mA or Voltage

    Download
  • Thumbnail of document Manual - DMD4059-DC DIN Rail Conditioners Convert Bridge Inputs to mA or Voltage
    Download

    Manual - DMD4059-DC DIN Rail Conditioners Convert Bridge Inputs to mA or Voltage

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more