Skip to main content
Press Enter
OMEGA

DRSL-DC2 DIN Rail Conditioner Series w/Process Input, High accuracy

Isolated DIN Rail Signal Conditioner

Normally ships in
2-3 weeks
Have questions? We're here to help!
Have questions? We're here to help!
Configure

Supported Applications

The Omega DRSL series comprises isolated DIN rail signal conditioners designed for the galvanic isolation and conversion of process voltage or current signals. These units interface field instrumentation with SCADA systems or PLC equipment, providing surge suppression and eliminating ground loops in industrial control environments.

Operating Conditions & Performance

The series delivers high accuracy performance rated at <±0.05% of span with a temperature coefficient of <±0.01% of span/°C. Signal response time is specified as <7 ms (0 to 90%, 100 to 10%). The units operate within an ambient temperature range of -25 to 70°C (-13 to 158°F) and a storage temperature range of -40 to 85°C (-40 to 185°F). Relative humidity tolerance is rated at 0 to 95% RH non-condensing. The enclosure carries an IP20 protection degree, suitable for Pollution Degree 2 and Measurement/Overvoltage Category II installation areas.

Electrical isolation separates input, output, and supply circuits with a working voltage of 300 Vac and a test voltage of 2.5 kVac. The signal-to-noise ratio exceeds 60 dB. EMC immunity influence is rated at <±0.5% of span, meeting NAMUR NE 21 A Criterion for extended immunity (Burst: <±1% of span).

Input and Output Specifications

The series supports configurable measurement ranges via DIP-switch selection:

• Current Input: Measurement range up to 0 to 20.5 mA; functional range 0 to 23 mA. Programmable ranges include 0 to 20 mA and 4 to 20 mA.
• Voltage Input: Measurement range up to 0 to 10.25 V; functional range includes 0 to 11.5 V or 0 to 5.75 V depending on configuration. Programmable ranges include 0 to 5 V, 1 to 5 V, 0 to 10 V, and 2 to 10 V.
• Current Output: Signal range up to 0 to 20.5 mA (span); programmable for 0 to 20 mA or 4 to 20 mA with a maximum load of 600 Ω at 23 mA and current limit ≤28 mA.
• Voltage Output: Signal range up to 0 to 10 V; programmable for 0 to 10, 2 to 10, 0 to 5, or 1 to 5 V with a minimum load of >10 kΩ.

The unit provides power supply capability for 2-wire transmitters at >17V/20 mA. Power consumption is 1.2 W max (internal consumption 0.4 W typical / 0.65 W max).

Power and Isolation

The series operates on a power supply of 16.8 to 31.2 Vdc, delivered via Power Rail or connectors.

Configuration Options

The DRSL-DC2 model is the primary isolated DIN rail signal conditioner in this series. The slimline housing measures 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5") and weighs approximately 70 g (0.15 lb). Mounting is designed for DIN EN 60715 - 35 mm rails.

Electrical connections utilize screw terminals compatible with stranded wire sizes from 0.13 to 2.5 mm² / AWG 26 to 12, requiring a torque of 0.5 Nm for secure termination.

Available Accessories

The series supports the following optional accessories for installation and power distribution:
• DRSL-PWR-RAIL: Power rail with cover and two end covers (one right hand, one left hand), 1 m (3.3') length.
• DRSL-PCU: Power connector unit providing 24 Vdc/2.5 A output to the power rail.
© DRSL-MOD-STOP: Module stop screwed onto the power rail to support and hold mounted devices.

Certifications and Warranty

The series carries CE, UL cUL US, and RoHS certifications. A 1-year warranty is standard; an OMEGACARE™ extended warranty program is available for models shown on this page.

Key Product Differences

The bundle enumerates two variants within the series: DRSL-DC1 and DRSL-DC2. The detailed specifications provided in the source data sheet apply to the DRSL-DC2 model, described as an isolated DIN rail signal conditioner.

• Isolation and Conversion of Process Voltage or Current Signals
• Power Supply and Signal Isolator for 2-Wire Transmitter
• Slimline Housing—Only 6 mm (0.24') Wide
• Multiple Signal Ranges (DIP-Switch Selectable)
Accuracy± 0.05 %
ApprovalsCE, UL, RoHS
Calibration Temperature, Max28 °C
Calibration Temperature, Min 20 °C
Conversion Rate1:1
Current Measurement Range0 to 20.5 mA
Electrical Output0 to 20.5 mA
EMC Immunity NoteExtended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
Enclosure RatingsIP20
Height113 mm
InstallationPollution degree 2 and measurement/overvoltage category II
Length115 mm
Load ResistanceCurrent Output: 23 mA/600 Ω max
MountingDIN Rail 35 mm Standard, EN 60715
MTBF284 yrs
Noise Calibration>60 dB
Operating Temperature, Max70 °C
Operating Temperature, Min-25 °C
Relative Humidity0 to 95% RH (non-condensing)
Response Time< 7 ms
Response Time NoteResponse Time (0 to 90%, 100 to 10%): <7 ms
Screw Terminal Torque0.5 Nm
Series IDDRSL-DC1-DC2-Srs-Sig-Cond
StabilityLoad Stability: ≤0.01% of span/100 Ω
Storage Temperature, Max85 °C
Storage Temperature, Min-40 °C
Supply Power TypeDC
Supply Voltage16.8 to 31.2 Vdc
Temperature Coefficient<±0.01% of span/°C
Weight70 g
Width6.1 mm
Wire Gauge26 to 12 AWG
  • Download

    Data Sheet - DRSL-DC2 DIN Rail Conditioner Series w/Process Input, High accuracy

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more