DRSL-DC4 DIN Rail Signal Conditioner for Bipolar Process Inputs
Bipolar Isolated DIN Rail Signal Conditioner for Process Signals
Supported Applications
The Omega DRSL-DC4 is a bipolar isolated DIN rail signal conditioner designed for process signals. It provides galvanic isolation and converts bipolar process voltage and current inputs to unipolar output signals suitable for SCADA or PLC systems. The device eliminates ground loops and supports the measurement of floating signals.
Operating Conditions & Performance
The DRSL-DC4 operates within an ambient temperature range of -25 to 70°C (-13 to 158°F) with a storage temperature capability from -40 to 85°C (-40 to 185°F). It is rated for relative humidity between 0 to 95% RH non-condensing and carries an IP20 protection degree. The unit meets Pollution Degree 2 and Measurement/Overvoltage Category II installation area requirements.
Performance specifications include a response time of <7 ms (or <44 ms selectable) for the 0 to 90% rise and 100 to 10% fall, with an accuracy of <±0.05% of span. The signal-to-noise ratio exceeds 60 dB, and the cut-off frequency is >100 Hz or 10 Hz (selectable via DIP-switch). EMC immunity influence is specified at <±0.5% of span, while extended EMC immunity under NAMUR NE 21, A Criterion, Burst conditions remains below ±1% of span.
Input and Output Ranges
• Bipolar Current Input: Programmable ranges include ±10 mA and ±20 mA. The functional range extends from -23 to 23 mA with an input voltage drop of <1V @ 23 mA.
• Bipolar Voltage Input: Programmable ranges are available for ±5 V and ±10 V, supporting a functional range of -11.5 to 11.5 V with an input resistance ≥1 MΩ.
• Unipolar Current Output: Configurable signal ranges include 0 to 20 mA and 4 to 20 mA. The output supports a load of up to 600 Ω (per channel) at 23 mA, with a current limit ≤28 mA.
• Unipolar Voltage Output: Programmable signal ranges include 0 to 10 V, 2 to 10 V, 0 to 5 V, and 1 to 5 V. The functional range is 0 to 11.5 V with a minimum load resistance of >10 kΩ.
Isolation and Power
The unit features galvanic isolation between input, output, and supply circuits. Isolation voltage (test) is rated at 2.5 kVac, with an isolation working voltage of 300 Vac. The Mean Time Between Failures (MTBF) exceeds 241 years according to IEC 61709 (SN29500). Power supply requirements are 16.8 to 31.2 Vdc via power rail or connectors, with a maximum power consumption of 0.8 W.
Configuration Options
The DRSL-DC4 series is configured for DIN EN 60715 - 35 mm rails and features a slimline housing measuring 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5"). The unit weighs approximately 70 g (0.15 lb). Factory-calibrated ranges are configurable via DIP switches, and the device supports DIN rail mounting without an air gap.
Connections
The signal conditioner utilizes screw terminals for electrical connections. It accepts stranded wire sizes from 0.13 x 2.5 mm²/AWG 26 to 12 with a recommended screw terminal torque of 0.5 Nm.
Approvals and Certifications
• CE
• UL US
• RoHS
• 1 YEAR WARRANTY (OMEGACARE™ Extended Warranty Program available)
Key Product Differences
The primary model in this series is the DRSL-DC4, described as a bipolar isolated DIN rail signal conditioner for process signals. The series supports specific accessory configurations to facilitate installation and power distribution:
• DRSL-PWR-RAIL: Power rail with cover and two end covers (one right hand, one left hand), 1 m (3.3') length.
• DRSL-PCU: Power connector unit providing 24 Vdc/2.5 A output to the power rail.
• DRSL-MOD-STOP: Module stop screwed onto the power rail to support and hold mounted devices.
| Approvals | CE, UL, RoHS |
| Bandwidth | >100 Hz or 10 Hz (Selectable Via DIP-Switch) |
| Calibration Temperature, Max | 28 °C |
| Calibration Temperature, Min | 20 °C |
| Electrical Output | 0 to 23 mA |
| EMC Immunity Note | Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span |
| Enclosure Ratings | IP20 |
| Height | 113 mm |
| Installation | Pollution degree 2 and measurement/overvoltage category II |
| Isolation | 300 Vac |
| Length | 115 mm |
| Load Resistance | Current Output: 23 mA/600 Ω max, Voltage Output:>10 kΩ min |
| Mounting | DIN Rail 35 mm Standard, EN 60715 |
| MTBF | 241 yrs |
| Noise Calibration | >60 dB |
| Operating Temperature, Max | 70 °C |
| Operating Temperature, Min | -25 °C |
| Power Consumption | 0.8 W, Internal - max 0.65 W |
| Relative Humidity | 0 to 95% RH (non-condensing) |
| Screw Terminal Torque | 0.5 Nm |
| Series ID | DRSL-DC4-Bipolar-Sig-Cond |
| Span, Max | Corresponds to the presently selected DIP switch output range |
| Stability | Load Stability: ≤0.002% of span/100 Ω |
| Storage Temperature, Max | 85 °C |
| Storage Temperature, Min | -40 °C |
| Supply Power Type | DC |
| Weight | 70 g |
| Width | 6.1 mm |
| Wire Gauge | 26 to 12 AWG |
OMEGADRSL-PWR-RAIL
Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length
Call Today!
800-567-8686Normally ships in 2-3 weeks
OMEGADRSL-PCU
Power connector unit, 24 Vdc/2.5 A output to power rail
Call Today!
800-567-8686Normally ships in 2-3 weeks
OMEGADRSL-MOD-STOP
Module stop (screwed onto DIN rail to support and hold mounted devices)
Call Today!
800-567-8686Normally ships in 2-3 weeks