Skip to main content
Press Enter
OMEGA

DRSL-DC4 DIN Rail Signal Conditioner for Bipolar Process Inputs

Bipolar Isolated DIN Rail Signal Conditioner for Process Signals

Have questions? We're here to help!
Have questions? We're here to help!

 The DRSL-DC4 bipolar isolated DIN rail signal conditioner provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. The DRSL-DC4 can be used for signal conversion of standard bipolar analog process signals into unipolar analog signals. The unit offers isolation between input, output and supply, provides surge suppression and protects control systems from transients and noise.

 
The DRSL-DC4 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).
 
• Isolation and Conversion of Bipolar Process Voltage and Current Signals to Unipolar Signals
• Slimline Housing—Only 6 mm (0.24') Wide
• Multiple Signal Ranges (DIP-Switch Selectable)
• High Accuracy, <0.05% of Selected Rang
NAMUR NE 21, A Criterion, Burst<±1% of span
Screw Terminal Torques0.5 Nm
Wire Size0.13 x 2.5 mm²/AWG 26 to 12 stranded wire
DIN Rail TypeDIN EN 60715 - 35 mm
Weight70 g (0.15 lb) approx
Dimensions113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Mechanical
Installation AreaPollution degree 2 and measurement/overvoltage category II
Protection DegreeIP20
Relative Humidity0 to 95% RH non-condensing
Calibration Temperature20 to 28°C (68 to 82°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Operating Temperature-25 to 70°C (-13 to 158°F)
Environmental
Extended EMC Immunity
EMC Immunity Influence<±0.5% of span
Temperature Coefficient<±0.01% of span/°C
SpanCorresponds to presently selected DIP switch output range
Accuracy: <±0.05% of span
Response Time (0 to 90%, 100 to 10%)<7 ms or <44 ms
Cut-Off Frequency (3 dB)>100 Hz or 10 Hz (selectable via DIP-switch)
Signal/Noise Ratio>60 dB
MTBF>241 years, according to IEC 61709 (SN29500)
Isolation Voltage (Working)300 Vac
Isolation Voltage (Test)2.5 kVac
IsolationInput/output/supply
Internal Consumption0.4 W typical/0.65 W max
Power Consumption0.8 W max
Supply Voltage (via Power Rail or Connectors)16.8 to 31.2 Vdc
General
Load>10 kΩ min
Functional Range0 to 11.5V
Programmable Signal Ranges0 to 10V, 2 to 10V, 0 to 5V, 1 to 5V
Voltage Output
Current Limit≤28 mA
Load Stability≤0.002% of span/100 Ω
Load23 mA/600 Ω max (per channel)
Functional Range0 to 23 mA
Programmable Signal Ranges0 to 20 mA, 4 to 20 mA
Current Output
Output
Input Resistance≥1 MΩ
Functional Range-11.5 to 11.5V
Programmable Ranges±5V, ±10V
Voltage Input
Input Voltage Drop<1V @ 23 mA
Functional Range, Current Input-23 to 23 mA
Programmable Measurement Ranges±10 mA, ±20 mA
Current Input
Input
  • Thumbnail of document Data Sheet - DRSL-DC4 DIN Rail Signal Conditioner for Bipolar Process Inputs
    Download

    Data Sheet - DRSL-DC4 DIN Rail Signal Conditioner for Bipolar Process Inputs

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more