Skip to main content
Press Enter
OMEGA

DRSL-LPI-2 DIN Rail Input loop Powered Isolators w/ 1 or 2 Channels

DIN Rail Input Loop-Powered Isolators

Normally ships in
2-3 weeks
Have questions? We're here to help!
Have questions? We're here to help!
Configure

Supported Applications

The Omega DRSL-LPI Series consists of DIN Rail Input Loop-Powered Isolators designed for SCADA or PLC systems. These units provide galvanic isolation and a 1:1 conversion of standard current signals (0 to 20.5 mA). The series is engineered to eliminate ground loops, suppress surges, and protect against transients and noise in industrial signal conditioning applications.

Operating Conditions & Performance

The DRSL-LPI Series operates within an ambient temperature range of -25 to 70°C (-13 to 158°F) with a storage capability from -40 to 85°C (-40 to 185°F). The devices function in relative humidity levels of 0 to 95% RH non-condensing and carry an IP20 protection degree. Performance specifications include an absolute accuracy (at 25°C) of ±10 μA + 0.05% of max value of selected span, with a response time (<5 ms). The series supports a functional current input range of 0 to 23 mA and is NAMUR NE43 compliant for fault indication.

Electrical isolation parameters include an Isolation Voltage (Test) of 2.5 kVac and an Isolation Voltage (Working) of 300 Vac. The Signal/Noise Ratio exceeds 60 dB with a Cut-Off Frequency (3 dB) of 100 Hz.

Configuration Options

The series is available in two channel configurations: the DRSL-LPI-1 for single-channel applications and the DRSL-LPI-2 for dual-channel requirements. Both models feature a slimline housing with dimensions of 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5") and weigh approximately 70 g (0.15 lb).

Key configurable parameters and specifications include:

• Power Supply: Loop Powered, utilizing the analog input current signal loop.
• Input Signal Range: 0 to 20.5 mA (Signal Conversion) with a functional range up to 0 to 23 mA.
• Output Load: Maximum of 600 Ω, with an output voltage limit of 17.5V.
• Mechanical Mounting: Designed for DIN EN 60715 - 35 mm rails using screw terminals compatible with wire sizes from 0.13 x 2.5 mm²/AWG 26 to 12 stranded wire (Screw Terminal Torque: 0.5 Nm).
• Approvals: CE, UL US, RoHS, and NAMUR NE 21, A Criterion.

Optional accessories include the RAIL-35-1 (35 mm DIN rail, 1 m length) and DRSL-MOD-STOP module stop for supporting mounted devices. The OMEGACARE™ extended warranty program is available to extend the standard 1-year warranty to 2 years when ordered with OCW-1.

Key Product Differences

The primary distinction within the DRSL-LPI Series lies in channel count:

• DRSL-LPI-1: A DIN rail input loop-powered isolator configured for 1 channel operation.
• DRSL-LPI-2: A DIN rail input loop-powered isolator configured for 2 channels, maintaining the same slimline profile and performance characteristics as the single-channel model.

• 1 Channel (DRSL-LPI-1) or 2 Channel (DRSL-LPI-2) Input Loop Powered Isolators
• Powered by the Analog Input Current Signal Loop
• 1:1 Signal Ratio
• Low Input Voltage Drop
Accuracy±10 µA + 0.05 %
ApprovalsCE, UL, RoHS
Bandwidth100 Hz
Calibration Temperature, Max28 °C
Calibration Temperature, Min20 °C
Conversion Rate1:1
Current Measurement Range0 to 20.5 mA
Electrical Output0 to 20 mA
EMC Immunity NoteExtended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
Enclosure RatingsIP20
Height113 mm
Input Range NoteCurrent; Signal Conversion: 1 to 1; Functional Range: 0 to 23 mA (NAMUR NE43 compliant); Start up Current: 10 µA typical; Input Overload: 50 mA max; Input to Output Voltage Drop:1.25V + (0.015 x Vout)where Vout = Iout x Routput, typical; Input Voltage Drop:(Unit voltage drop) + Vout
Input TypeCurrent
InstallationPollution degree 2 and measurement/overvoltage category II
IsolationIsolation Voltage (Test): 2.5 kVac ;Isolation Voltage (Working):300 Vac
Length115 mm
MountingDIN Rail 35 mm Standard, EN 60715
Noise Calibration>60 dB
Operating Temperature, Max70 °C
Operating Temperature, Min-25 °C
Output DetailOutput Load: 600Ω max Output Load Stability: <0.01% of span/100 Ω (span = 0 to 20 mA) Voltage Limit: 17.5V
Output Signal Current
Power Consumption30 mW
Relative Humidity0 to 95% RH (non-condensing)
Response Time< 5 ms
Response Time NoteResponse Time (0 to 90%, 100 to 10%): <5 ms
Screw Terminal Torque0.5 Nm
Series IDDRSL-LPI-Srs-Loop-Pwr-Iso
StabilityLoad Stability: ≤0.01% of span/100 Ω
Storage Temperature, Max85 °C
Storage Temperature, Min-40 °C
Supply Power TypeLoop Powered
Temperature Coefficient≤±2 µA/°C
Voltage Loss(Unit voltage drop) + Vout
Weight70 g
Width6.1 mm
Wire Gauge26 to 12 AWG
  • Download

    Data Sheet - DRSL-LPI-2 DIN Rail Input loop Powered Isolators w/ 1 or 2 Channels

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more