DRSL-RTD-ISO DIN Rail RTD Input Signal conditioner/Low profile

RTD Input DIN Rail Signal Conditioners

Normally ships in
2-3 weeks
Have questions? We're here to help!
Have questions? We're here to help!
Configure

Supported Applications

The Omega DRSL-RTD Series consists of DIN rail signal conditioners designed to interface RTD inputs with SCADA systems or PLC equipment. The series converts signals from 2, 3, or 4-wire Pt100 RTDs into unipolar analog outputs suitable for industrial control environments.

Operating Conditions & Performance

The DRSL-RTD Series operates over an ambient temperature range of -25 to 70°C (-13 to 158°F) with a storage capability from -40 to 85°C (-40 to 185°F). The units support relative humidity levels of 0 to 95% RH non-condensing and carry an IP20 protection degree. Measurement ranges span -200 to 850°C (-328 to 1562°F) with a sensor current below 150 μA.

Accuracy specifications differ by model: the DRSL-RTD offers better than 0.2°C or ±0.1% of selected input range, while the isolated DRSL-RTD-ISO provides better than 0.1°C or ±0.05% of selected input range. Response time is selectable at <30 ms/300 ms (0 to 90%, 100 to 10%). The series includes broken sensor detection (>800 Ω) and shorted sensor detection (<18 Ω).

Configuration Options

The series supports configuration via DIP-switches for more than 1,000 factory-calibrated measurement ranges. Output signals are programmable to match specific system requirements.

• Output Signals: Current outputs include 0 to 20 mA and 4 to 20 mA; voltage outputs include 0 to 10 V, 2 to 10 V, 0 to 5 V, and 1 to 5 V.
• Power Supply: DRSL-RTD models accept 16.8 to 31.2 Vdc via connectors; DRSL-RTD-ISO models accept 16.8 to 31.2 Vdc via power rail or connectors.
• Isolation (DRSL-RTD-ISO Only): Provides 3-way isolation between input, output, and supply with a test voltage of 2.5 kVac (reinforced) and working voltage of 300 Vac.
• Error Detection: Sensor error detection is selectable via DIP-switch for enable or none; incorrect DIP-switch settings trigger specific out-of-range outputs.

Mechanical installation features DIN EN 60715 - 35 mm rail mounting with screw terminals accepting wire sizes from 0.13 x 2.5 mm² / AWG 26 to 12 stranded wire (torque: 0.5 Nm). The unit dimensions are 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5") with an approximate weight of 70 g (0.15 lb).

Key Product Differences

The series is available in two primary configurations:

• DRSL-RTD: Non-isolated RTD input DIN rail signal conditioner.
• DRSL-RTD-ISO: Isolated RTD input DIN rail signal conditioner offering surge suppression and protection against transients and noise. This model requires the DRSL-PWR-RAIL power rail for operation when using the rail interface.

Accessories available for the series include the DRSL-PWR-RAIL (1 m length, with cover and end covers), DRSL-PCU (power connector unit, 24 Vdc/2.5 A output), and DRSL-MOD-STOP (module stop). The OMEGACARE™ extended warranty program is available for these models.

• DRSL-RTD Non-Isolated and DRSL-RTD-ISO Isolated Models
• 2, 3 or 4-Wire Pt100 RTD Input
• Pre-Calibrated Temperature Ranges Selectable via Dip-Switches
• Slimline Housing—Only 6 mm (0.24') Wide
Accuracy DetailBetter than 0.2°C or ±0.1% of selected range
ApprovalsCE, UL, RoHS
Calibration Temperature, Max28 °C
Calibration Temperature, Min20 °C
Electrical Output4 to 20 mA
EMC Immunity NoteNAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)
Enclosure RatingsIP20
Height113 mm
Input Range NoteSensor Current, RTD: <150 µA;Sensor Cable Specifications: 50 Ωper wire or 50 nF;Effect of Sensor Cable Resistance (3 or 4-wire RTD): <0.002 Ω/Ω;Broken Sensor Detection: >800 Ω;Shorted Sensor Detection: <18 Ω
Input TypeRTD
InstallationPollution degree 2 and measurement/overvoltage category II
Length115 mm
MountingDIN Rail 35 mm Standard, EN 60715
Noise Calibration>60 dB
Number of Inputs1
Operating Temperature, Max70 °C
Operating Temperature, Min-25 °C
Output DetailCurrent: Range Limits(NAMUR NE43 Out of Range):Below 3.8 mA or above 20.5 mA for 4 to 20 mA output; 0 mA or above 20.5 mA for 0 to 20 mA output Sensor Error Detection(Dip Switch Selectable for Enable or None): Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output Incorrect DIP-Switch Setting Identification: Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output Output Error Level: DIP switch selectable for upscale or downscale. Voltage: Range Limits (Out of Range):Range ±2.5% Sensor Error Detection (Dip Switch Selectable for Enableor None): 0V or selected range + 10% Incorrect DIP-Switch Setting Identification: 0V Output Error Level: DIP switch selectable for upscale or downscale
Output SignalCurrent, Voltage
Power Consumption0.7 W, Internal - 0.65 W
Relative Humidity0 to 95% RH (non-condensing)
Response Time< 30 ms
Response Time NoteResponse Time (0 to 90%, 100 to 10%): <30 ms/300 ms (selectable, provides either fast response or signal dampening as needed)
Screw Terminal Torque0.5 Nm
Series IDDRSL-RTD-Srs-Sig-Cond
StabilityLoad Stability: ≤0.01% of span/100 Ω
Storage Temperature, Max85 °C
Storage Temperature, Min-40 °C
Supply Power TypeDC
Supply Voltage16.8 to 31.2 Vdc
Temperature Coefficient≤±0.02°C/°C
Voltage Output Range0 to 10 Vdc
Weight70 g
Width6.1 mm
Wire Gauge26 to 13 AWG
  • Download

    Data Sheet - DRSL-RTD-ISO DIN Rail RTD Input Signal conditioner/Low profile