DRSL-RTD-LP Non Isolated Loop Powered DIN Rail RTD input Conditioner

RTD Input Non-Isolated DIN Rail Loop-Powered Signal Conditioner

Normally ships in
2-3 weeks
Have questions? We're here to help!
Have questions? We're here to help!

Supported Applications

The Omega DRSL-RTD-LP is a non-isolated, loop-powered DIN rail signal conditioner designed to interface 2-, 3-, or 4-wire Pt100 RTD temperature sensors with SCADA systems and PLC equipment. The unit converts the sensor input into a passive analog current output signal suitable for industrial process monitoring.

Operating Conditions & Performance

The DRSL-RTD-LP operates within an ambient temperature range of -25 to 70°C (-13 to 158°F) and supports storage temperatures from -40 to 85°C (-40 to 185°F). It is rated for environments with relative humidity up to 95% RH non-condensing. The device provides an accuracy of better than 0.2°C or ±0.1% of the selected range, with a temperature coefficient of ≤±0.02°C/°C.

Performance specifications include:

• Input Range: -200 to 850°C (-328 to 1562°F)
• Sensor Current (RTD): <150 μA
• Response Time: <30 ms/300 ms (selectable, 0 to 90% / 100 to 10%)
• Signal-to-Noise Ratio: >60 dB
• EMC Immunity Influence: <±0.5% of span (Extended EMC: NAMUR NE 21, A Criterion)

The unit is designed for use in Pollution Degree 2 and Overvoltage Category II installations.

Power and Electrical Limits

• Supply Voltage: 3.3 to 35 Vdc (loop-powered)
• Voltage Drop: 3.3 Vdc
• Max Power Consumption: 1 W max (Internal: 0.65 W max)
• Load Resistance: ≤(V_supply - 3.3)/0.023 Ω
• Sensor Cable Specifications: 50Ω per wire or 50 nF
• Effect of Sensor Cable Resistance (3 or 4-Wire RTD): <0.002Ω/Ω

Configuration Options

The DRSL-RTD-LP series is configurable via DIP switches to select from over 1,000 factory-calibrated measurement ranges. The device supports programmable output signal ranges of 0 to 20 mA and 4 to 20 mA.

Input and Output Configuration

• Input Type: 2, 3, or 4-wire Pt100 RTD
• Broken Sensor Detection: >800Ω (Output: Below 3.5 mA or above 23 mA)
• Shorted Sensor Detection: <18Ω
• NAMUR NE43 Range Limits: Below 3.8 mA or above 20.5 mA
• Error Identification: Incorrect DIP-switch settings trigger output levels below 3.5 mA or above 23 mA.
• Output Error Level: Selectable for upscale or downscale via DIP switch.

Mechanical and Environmental Features

• Housing Protection Degree: IP20
• DIN Rail Type: DIN EN 60715 - 35 mm (requires enclosure for live part protection)
• Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
• Weight: Approx. 70 g (0.15 lb)
• Wire Size: 0.13 to 2.5 mm² / AWG 26 to 12 stranded wire
• Screw Terminal Torque: 0.5 Nm

Key Product Differences

The DRSL-RTD-LP is a specific model within the broader DRS-L family of signal conditioners, distinguished by its loop-powered architecture and non-isolated design for Pt100 RTD inputs. Unlike isolated variants (e.g., DRS-L-RTD-ISO) or thermocouple models in the same manual scope, this unit is powered directly from the host output current signal loop.

Available accessories include:

• RAIL-35-1: 35 mm (1.4") DIN rail, 1 m (3.3') length
• DRSL-MOD-STOP: Module stop screwed onto the DIN rail to support and hold mounted devices.

• 2, 3 or 4-Wire Pt100 RTD Input
• Powered By the Host (Output) Current Signal Loop
• High Accuracy Better Than 0.2°C or 0.1% of Selected Range
• Slimline 6 mm (0.24') Housing
ApprovalsCE, UL, RoHS
Calibration Temperature, Max28 °C
Calibration Temperature, Min20 °C
Electrical Output0 to 20 mA, 4 to 20 mA
EMC Immunity NoteNAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)
Enclosure RatingsIP20
Height113 mm
InstallationPollution degree 2 and measurement/overvoltage category II
Length115 mm
MountingDIN Rail 35 mm Standard, EN 60715
Noise Calibration>60 dB
Operating Temperature, Max70 °C
Operating Temperature, Min-25 °C
Power Consumption1 W, Internal - 0.65 W
Relative Humidity0 to 95% RH (non-condensing)
Screw Terminal Torque0.5 Nm
Series IDDRSL-RTD-LP-Sig-Cond
StabilityLoad Stability: ≤0.01% of span/100 Ω
Storage Temperature, Max85 °C
Storage Temperature, Min-40 °C
Voltage Loss3.3 Vdc
Weight70 g
Width6.1 mm
Wire Gauge26 to 13 AWG
  • Download

    Data Sheet - DRSL-RTD-LP Non Isolated Loop Powered DIN Rail RTD input Conditioner

    Download
  • Download

    Manual - DRSL-RTD-LP Non Isolated Loop Powered DIN Rail RTD input Conditioner

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more