Skip to main content
Press Enter
OMEGA

DRSL-U DIN Rail Universal Input Signal Conditioner w/Slim Housing

Isolated Universal Input DIN Rail Signal Conditioner

Normally ships in
2-3 weeks
Have questions? We're here to help!
Have questions? We're here to help!
Configure

Supported Applications

The Omega DRSL-U is an isolated universal input DIN rail signal conditioner designed for the galvanic isolation of process signals to SCADA systems or PLC equipment. It accepts thermocouple, RTD, linear resistance, potentiometer, voltage, or current inputs and converts them to a linear voltage or current output. The unit eliminates ground loops, allowing for floating signal measurements.

Operating Conditions & Performance

The DRSL-U operates within an ambient temperature range of -25 to 70°C (-13 to 158°F) and a storage temperature of -40 to 85°C (-40 to 185°F). It is rated for humidity from 0 to 95% RH non-condensing with an enclosure rating of IP20. The device features excellent EMC performance with 50/60 Hz noise suppression.

Response time specifications are ≤1 s for Temperature Input (0 to 90%, 100 to 10%) and ≤400 ms for mA/V input (0 to 90%, 100 to 10%). Basic accuracy varies by input type, including ±0.2°C for Pt100 sensors, ±1.0°C for Thermocouple Types E, J, K, L, N, T, and U, and ±16 μA for mA inputs.

Measurement Ranges

The series supports the following documented input ranges:

• Thermocouples: Types J (-100 to 1200°C), K (-180 to 1372°C), T (-200 to 400°C), E (-100 to 1000°C), R and S (-50 to 1760°C), B (0 to 1820°C), N (-180 to 1300°C), L (-200 to 900°C), U (-200 to 600°C), W3/W5 (0 to 2300°C), and LR (-200 to 800°C).
• RTDs: Pt100 (-200 to 850°C) and Ni100 (-60 to 250°C).
• Linear Resistance/Potentiometer: 0 to 10,000 Ω or 10 to 100 kΩ.
• Voltage/Current: 0 to 12 V, 4 to 20 mA, and 0 to 20 mA inputs are supported with output options of 0 to 20 mA, 4 to 20 mA, or 0 to 10 Vdc.

Power & Load Specifications

The unit requires a power supply of 16.8 to 31.2 Vdc via power rail or connectors. The maximum load resistance is specified as 20 mA/600 Ω/15 Vdc max.

Configuration Options

The DRSL-U features a slimline housing with overall dimensions of 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5") and weighs approximately 70 g (0.15 lb). It utilizes screw terminals for electrical connections and is designed for DIN Rail Mounting.

Configuration is performed using the DRSL-DISPLAY programming interface, which plugs into a docking station adaptor. The device uses electronic hardware switches to set parameters without opening the enclosure or adjusting internal DIP-switches. The DRSL-DISPLAY features a 4 line LCD display with scrolling help text in English, French, German, Italian, Spanish, Danish, and Swedish.

Available Accessories

• DRSL-PWR-RAIL: Power rail (with cover and two end covers), 1 m length.
• DRSL-PCU: Power connector unit, 24 Vdc/2.5 A output to power rail.
• DRSL-MOD-STOP: Module stop for supporting mounted devices on the power rail.

Certifications & Warranty

The series carries CE, UL, cUL, and RoHS approvals. A 1 YEAR WARRANTY is included, with an OMEGACARE™ extended warranty program available covering parts, labor, and equivalent loaners.

Key Product Differences

The primary model in this series is the DRSL-U (Isolated universal input signal conditioner). Configuration requires separate ordering of the DRSL-DISPLAY interface and the DRSL-ADAPTOR docking station. The device supports multiple sensor families including Thermocouple, RTD, Linear Resistance, Potentiometer, Voltage, and Current inputs within a single isolated housing

• Universal Input–Accepts Thermocouple, RTD, Linear Resistance, Potentiometer, Voltage or Current Input
• Easily Configured Using DRSL-DISPLAY Programming Interface or electronic hardware switch
• Slimline Housing–Only 6 mm (0.24') Wide
• High Accuracy
ApprovalsCE, UL, RoHS
Calibration Temperature, Max28 °C
Calibration Temperature, Min20 °C
Electrical Output4 to 20 mA
EMC Immunity NoteNAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)
Enclosure RatingsIP20
Height113 mm
InstallationPollution degree 2 and measurement/overvoltage category II
Isolation300 Vac
LED IndicatorsStatus LED: Green LED indicates ;operational status of the unit and ;input sensor; Normal Operation: Flashes for;15 ms at 13 Hz rate;Sensor Error: Flashes for 15 ms;at 1 Hz rate;Hardware Failure: LED off
Length115 mm
Load ResistanceCurrent Output: 20 mA/600 Ω/15 Vdc max, Voltage Output:>10 kΩ;
MountingDIN Rail 35 mm Standard, EN 60715
Noise Calibration>60 dB
Operating Temperature, Max70 °C
Operating Temperature, Min-25 °C
Power Consumption1.2 W, Internal - max 0.65 W
Relative Humidity0 to 95% RH (non-condensing)
Screw Terminal Torque0.5 Nm
Series IDDRSL-U-Univ-Input-Sig-Cnd
StabilityLoad Stability: ≤0.01% of span/100 Ω
Storage Temperature, Max85 °C
Storage Temperature, Min-40 °C
Supply Power TypeDC
Temperature Coefficient NoteAll Input Types: ≤± 0.01% of span/°C
Weight70 g
Width6.1 mm
Wire Gauge26 to 12 AWG
  • Download

    Data Sheet - DRSL-U DIN Rail Universal Input Signal Conditioner w/Slim Housing

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more