Skip to main content
Press Enter
OMEGA

DRST-AC DIN Rail AC Current & Voltage Transmitter

Measures AC Current and Voltage Signals

Have questions? We're here to help!
Have questions? We're here to help!

 Application

• The 0 to 5 AAC RMS range makes it possible to accurately measure a typical current transformer.
• The 0 to 300 Vac RMS range allows accurate supply voltage monitoring.
• DRST-AC measures standard input ranges, and can be freely configured to customer-defined input range.
• Converts narrow AC current/voltage inputs to wide bipolar or unipolar outputs, e.g. 0 to 1 VAMS input = ±10 volt or 4 to 20 mA output with a minimum span of 0.5 AAC RMS or 0.5 Vac RMS.
• Configurable input limits control the output value for increased safety.
Technical Characteristic
• The latest analog and digital techniques are used to obtain maximum accuracy and immunity to interference.
• Possibility of output safety feedback by selecting S4 to 20 mA output.
• The current output can drive up to 800 Ω, with an adjustable response time of 0.0 to 60.0 seconds.
• Exceptional mA output load stability of <0.001% of span/100 Ω
. • Meets the NAMUR NE21 recommendations, ensuring high accuracy in harsh EMC environments.
• Meets the NAMUR NE43 recommendations, allowing the control system to easily detect an input error.
• Each unit is tested to a high 2.3 kVac, 3-port galvanic isolation level.
• Excellent signal to noise ratio of > 60 dB.
Mounting/Installation/Programming
• Very low power consumption means units can be mounted side by side without an air gap – even at 60°C ambient temperature.
• Configuration, monitoring, 2-point process calibration and more are accomplished using either the 4501 detachable display or the 4511 detachable digital communication enabler.
• All programming can be password-protected.
• UL and cUL Approval
• Measures AC Current and Voltage Signals
• Outputs Passive or Active Current Signals
• Response Time < 0.75 s and Excellent Accuracy Better Than 0.3%
["
NB<\/td>For custom configurable signal ranges, general accuracy and EMC specifications are 0.3% of full scale<\/td><\/tr>
UL<\/td>UL 508 \/ C22.2 no. 14<\/td><\/tr>
Approvals<\/td><\/td><\/tr>
RoHS<\/td>2011\/65\/EU<\/td><\/tr>
LVD<\/td>2014\/35\/EU<\/td><\/tr>
EMC<\/td>2014\/30\/EU<\/td><\/tr>
Observed Authority Requirements<\/td><\/td><\/tr>
Response Time, Programmable<\/td>0.0 to 60.0 s<\/td><\/tr>
Load (@ Voltage Output)<\/td>≥ 500 kΩ<\/td><\/tr>
V-Curve Function, 100-0-100%<\/td>1-0-1, 5-0-5 and 10-0-10 V<\/td><\/tr>
Programmable Signal Ranges<\/td>Direct or Inverted Action<\/td><\/tr>
Programmable Signal Ranges<\/td>±1, ±5 and ±10 V<\/td><\/tr>
Programmable Signal Ranges<\/td>0\/0.2 to 1; 0\/1 to 5 ; 0\/2 to 10; 1 to 0.2\/0; 5 to 1\/0; 10 to 2\/0 V<\/td><\/tr>
Voltage Output<\/td><\/td><\/tr>
Response Time, Programmable<\/td>00 to 60.0 s<\/td><\/tr>
Load Stability<\/td>≤ 0.001% of span \/ 100 Ω<\/td><\/tr>
Current Limit<\/td>± 28 mA (bipolar)<\/td><\/tr>
Current Limit<\/td>≤ 28 mA (unipolar)<\/td><\/tr>
Signal Range<\/td>-23 to +23 mA (bipolar)<\/td><\/tr>
Signal Range<\/td>3.5 to 30 V<\/td><\/tr>
Input Specifications<\/td><\/td><\/tr>
Of Span<\/td>= of selected standard range<\/td><\/tr>
<\/td>Extended EMC immunity: NAMUR NE21, A Criterion, Burst: < ±1% of span<\/td><\/tr>
EMC Immunity Influence<\/td>< ±0.5% of span*<\/td><\/tr>
Accuracy\t<\/td>Better than 0.3% of selected range*<\/td><\/tr>
Output Referred Common Mode Rejection Ratio<\/td>0.02 ppm\/VHz<\/td><\/tr>
Signal Dynamics, Output<\/td>18 bit
Signal\/Noise Ratio: > 60 dB<\/td><\/tr>
Signal Dynamics, Input<\/td>20 bit<\/td><\/tr>
Programming<\/td>Communication enabler\/Programming front DRSL-DISPLAY<\/td><\/tr>
Response Time (0...90%, 100...10%)<\/td>< 0.75 s<\/td><\/tr>
Response Time<\/td><\/td><\/tr>
Test Voltage<\/td>2.3 kVac
Working Voltage: 250 Vac (reinforced)\/500 Vac (basic)<\/td><\/tr>
Isolation Voltage<\/td><\/td><\/tr>
Internal Power Dissipation<\/td>≤ 2.5 W<\/td><\/tr>
Max. Required Power<\/td>≤ 1.8 W nom.<\/td><\/tr>
Supply Voltage, Universal<\/td>21.6 to 253 Vac, 50 to 60 Hz or 19.2 to 300 Vdc<\/td><\/tr>
Supply<\/td><\/td><\/tr>
Common Specifications<\/td><\/td><\/tr>
13.2 to 100 Hz<\/td>±0.7 g<\/td><\/tr>
2 to 13.2 Hz<\/td>±1 mm<\/td><\/tr>
Vibration<\/td>IEC 60068-2-9<\/td><\/tr>
Screw Terminal Torque<\/td>0.5 Nm<\/td><\/tr>
Wire Size<\/td>0.13 to 2.08 mm 2 AWG 26 to 14 stranded wire<\/td><\/tr>
DIN Rail Type<\/td>DIN EN 60715\/35 mm<\/td><\/tr>
Weight incl. 4501\/4511 (approx.)<\/td>285 g \/ 350 g<\/td><\/tr>
Weight Approx<\/td>250 g<\/td><\/tr>
Dimensions (HxWxD) w\/ 4501\/4511<\/td>109 x 23.5 x 116 \/ 131 mm<\/td><\/tr>
Dimensions (HxWxD)<\/td>109 x 23.5 x 104 mm<\/td><\/tr>
Mechanical Specifications<\/td><\/td><\/tr>
installation In<\/td>Pollution degree 2 and measurement\/overvoltage cat. II<\/td><\/tr>
Protection Degree<\/td>IP20<\/td><\/tr>
Relative Humidity<\/td>< 95% RH (non-cond.)<\/td><\/tr>
Calibration Temperature<\/td>20 to 28°C<\/td><\/tr>
Operating Temperature<\/td>-20 to 60°C<\/td><\/tr>
Environmental Conditions<\/td><\/td><\/tr>
Current Output<\/td><\/td><\/tr>
External Loop Supply<\/td>3.5 to 30 V<\/td><\/tr>
V-Curve Function, 100-0 to 100%<\/td>20-0 to 20 mA<\/td><\/tr>
Programmable Ranges<\/td>Direct or Inverted action<\/td><\/tr>
Programmable Ranges<\/td>0 to 20 and 4 to 20 mA<\/td><\/tr>
Passive 2-Wire mA Output<\/td><\/td><\/tr>
V-Curve Function, Active Signals, 100-0-100%:<\/td>20-0 to 20 mA<\/td><\/tr>
Load (@ Current Output)<\/td>≤ 800 Ω<\/td><\/tr>
Programmable Ranges<\/td>Direct or Inverted Action<\/td><\/tr>
Programmable Ranges<\/td>±10 and ±20 mA<\/td><\/tr>
Programmable Ranges<\/td>0 to 20, 4 to 20 and S4 to 20 mA<\/td><\/tr>
Active Unipolar and Bipolar mA Output<\/td><\/td><\/tr>
Output Specifications<\/td><\/td><\/tr>
Input Resistance<\/td>Nom. 3 MΩ","100 pF<\/td><\/tr>
Min. Measurement Range (Span)<\/td>0.5 Vac<\/td><\/tr>
Programmable Measurement Ranges<\/td>0 to 0.5, 0 to 1, 0 to 2.83, 0 to 5, 0 to 120, 0 to 230 and 0 to 300 Vac
Custom Configurable Signal Range: 0 to 300 Vac\/40 to 400 Hz<\/td><\/tr>
Signal Range<\/td>0 to 300 Vac\/40 to 400 Hz<\/td><\/tr>
Voltage Input<\/td><\/td><\/tr>
Input Resistance<\/td>Nom. < 0.07 Ω<\/td><\/tr>
Min. Measurement Range (Span)<\/td>0.5 AAC<\/td><\/tr>
Programmable Measurement Ranges<\/td>0 to 0.5; 0 to 1; 0 to 2.5 and 0 to 5 AAC
Custom Configurable Signal Range: 0 to 5 AAC\/40 to 400 Hz<\/td><\/tr>
Maximum Input Limit<\/td>6.00 AAC @ 40°C<\/td><\/tr>
Signal Range<\/td>0 to 5 AAC\/40 to 400 Hz<\/td><\/tr>
Current Input<\/td><\/td><\/tr><\/table>"]
  • Thumbnail of document Manual - DRST-AC DIN Rail AC Current & Voltage Transmitter
    Download

    Manual - DRST-AC DIN Rail AC Current & Voltage Transmitter

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more