DRST-FR DIN Rail Frequency Input Signal Conditioner

Programmable Signal Converter for Frequency

Normally ships in
2-3 weeks
Have questions? We're here to help!
Have questions? We're here to help!

Supported Applications

The Omega DRST-FR is a programmable converter designed for industrial applications. The device features a DIN rail mountable housing and is intended for use with hazardous electric voltages.

Operating Conditions & Performance

This series operates on a power supply of 24-230VDC / 24-230VAC. The device includes analog output voltage, analog output current, digital output 1 / relay 1, and digital output 2 / relay 2 capabilities.

Configuration Options

The DRST-FR series supports configurable terminal assignments for inputs, outputs, and power. The device includes status indicators labeled f_in (two instances) and error. Key configuration options include:

• Housing & Mounting: DIN rail mountable housing according to DIN 46277.
• Connections: Terminal block connections with a communication connector connected to input terminals.
• Outputs: Analog output voltage, analog output current, and two digital/relay outputs (digital output 1 / relay 1; digital output 2 / relay 2).
• Approvals & Safety: CE mark, Double insulation symbol, Ex devices approved acc. to ATEX directive.

The terminal assignments include specific functions for analog ground (Terminal 11), voltage and current outputs (Terminals 12/13), digital grounds and relay contacts (Terminals 21-24), power supply inputs (Terminals 31-33), and sensor input/supply lines (Terminals 42, 52).

Key Product Differences

The series model number guide follows the pattern DRST-FR - <Variant>, with examples including DRST-FR/A and DRST-FR/B. The device must only be connected to the programming unit Loop Link by way of the enclosed cable.

• Configurable with a standard PC and TXUN-KIT communications unit
• Pulse Calculator
• Frequency Generator
• Galvanic Isolation
Approvals NoteEMC:2014/30/EU, LVD:2014/35/EU
Calibration Temperature, Max28 °C
Calibration Temperature, Min20 °C
Electrical Output0 to 20 mA
Enclosure RatingsIP20
Frequency Measurement Range0 to 20 kHz
Fuse Rating400 mA SB / 250 Vac
Height109 mm
Isolation3750 Vac
Length130 mm
Linearity Error< 0.1% of span
Load ResistanceVoltage Output : ≥ 500 kΩ, Current Output : ≤ 600 Ω
MountingDIN Rail 46277
Noise Calibration>60 dB
Operating Temperature, Max60 °C
Operating Temperature, Min-20 °C
Optional Power Note0 to 999 s
Power Consumption3.5 W, Internal - 3 W
Relative Humidity<95% RH
Screw Terminal Torque0.5 Nm
Series IDDRST-FR-Freq-Sig-Cond
Signal Dynamics Output16 bit
StabilityLoad Stability: ≤0.01% of span/100 Ω
Supply Power TypeAC/DC
Update Rate20 ms
Warm Up Time1 min
Weight240 g
Width23.5 mm
  • Download

    Manual - DRST-FR DIN Rail Frequency Input Signal Conditioner

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more