Skip to main content
Press Enter
OMEGA

HX93BC Temp/RH Transmitter w/Display & Probe

Temperature/Relative Humidity Transmitters

Have questions? We're here to help!
Have questions? We're here to help!

 The HX93B and HX93BD Series transmitters provide remote and on-site monitoring of temperature and relative humidity. Both series output a linearized current or voltage signal proportional to the temperature and relative humidity. Relative humidity output is temperature compensated. Current output models enable placing of the transmitter at a remote location virtually any distance away from the measuring device. The HX93BD models feature a built-in digital display that indicates both temperature and relative humidity simultaneously. All models use an accurate digital sensor. A stainless steel mesh type filter, easily removable for cleaning, protects the sensor. Mounting screws are easily accessible inside the rugged, polycarbonate enclosure which protects the electronics to NEMA 13 (IP54) specifications.

• 4 to 20 mA, 0 to 1 Vdc, 0 to 5 Vdc or 0 to 10 Vdc Outputs for Both Temperature and Relative Humidity
• Rugged Industrial Splashproof Enclosure NEMA 13 (IP54)
• Accurate to ±0.6°C (0 to 50°C) and ±2.5% (10 to 90% Relative Humidity)
• New Models with Built-In Digital Display to Indicate Temperature and Relative Humidity
Relative Humidity±2.5% from 10 to 90% RH; ±3.5% from 5 to 10% and 90 to 95% RH; ±4% from 0 to 5% and 95 to 100% RH
HX93BDC±1.9°C from 0 to 50°C (32 to 122°F); ±2.6°C from -30 to 0°C (-22 to 32°F) and 50 to 75°C (122 to 167°F)
HX93BC- ±0.9°C from 0 to 50°C (32 to 122°F); ±1.6°C from -30 to 0°C (-22 to 32°F) and 50 to 75°C (122 to 167°F)
Temperature±0.6°C from 0 to 50°C (32 to 122°F); ±1.25°C from -30 to 0°C (-22 to 32°F) and 50 to 75°C (122 to 167°F) for all models except:
Accuracy
Relative Humidity0 to 100%
TemperatureStandard: -30 to 75°C (-22 to 167°F);Special: -20 to 75°C (-4 to 167°F)
Not for condensing humidity conditions.
Measuring Range
HX93BV2 Series12 to 30 Vdc
HX93B Series9 to 30 Vdc
Input Voltage Range30 Vdc maximum
ConnectionsLiquid-tight nylon with neoprene gland, for 2.50 to 8.00 mm (0.09 to 0.315") diameter cable; internal 6 position terminal block accepts 14 to 22 gauge wire
HX93B(*)-D (with Probe)80.01 L x 82.30 W x 183.13 D mm (3.15 x 3.24 x 7.21")
HX93B(*) (without Probe)80.01 L x 82.30 W x 55.63 D mm (3.15 x 3.24 x 2.19")
Dimensions
HousingGray polycarbonate, NEMA rated up to 13 (IP54)
Repeatability±0.1% RH, ±0.2°C (0.4°F)
Relative Humidity Response Time8 second typical
Temperature Response Time5 seconds minimum, 30 seconds maximum
Relative Humidity Temperature Compensation-30 to 75°C (-22 to 167°F)
HX93BV20 to 10 Vdc for 0 to 100% RH and -30 to 75°C (-22 to 167°F)
HX93BV10 to 5 Vdc for 0 to 100% RH and -30 to 75°C (-22 to 167°F)
HX93BV00 to 1 Vdc for 0 to 100% RH and -30 to 75°C (-22 to 167°F)
HX93BC or HX93BDC4 to 20 mA for 0 to 100% RH and -30 to 75°C (-22 to 167°F)
Output
Display Resolution:Relative Humidity: 0.1% RH
Temperature: 0.1°C (0.1°F)
Display Rate: 1 reading per second
Indicators: Two 4 digit backlit LCD
Display (HX93BD Series Only)
HX93B(*)-RP1352 g (12.4 oz)
HX93B(*)-D256 g (9.0 oz)
HX93B(*):251 g (8.9 oz)
Weight
TP-SP (Short Probe)ø16 x 71.88 L mm (ø0.63 x 2.83")
  • Thumbnail of document Data Sheet - HX93BC Temp/RH Transmitter w/Display & Probe
    Download

    Data Sheet - HX93BC Temp/RH Transmitter w/Display & Probe

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more