IsoPAQ-611/612 1 & 2 Channel Loop Powered Isolators

Provides galvanic separation for 0(4) - 20 mA standard signals, while transferring the measurement signal to the output w/ a high degree of accuracy

Starting at
$326.40CAD
Have questions? We're here to help!
Have questions? We're here to help!
Configure

The input loop-powered isolators IsoPAQ-611/612 provide galvanic separation for 0(4) … 20 mA standard signals, while transferring the measurement signal to the output with a high degree of accuracy.

The unit avoids interference voltage carry-over and effectively suppressing parasitic noise. The very low drop voltage of 2.3 V and the high level of accuracy work together to make the IsoPAQ-611 the first choice in system design.

Intelligent design and their consequential avoidance of highly integrated components result in extremely long service lives and reliability – without any falsification of the measurement signal.

The IsoPAQ-611/612 requires no additional power supply since the auxiliary power is obtained from the input signal without distorting it. This not only saves costs during installation, but also increases reliability.

Galvanic isolation across input and output
    Protection against erroneous measurements due to parasitic voltages or ground loops
No power supply required
    Saving costs since wiring is reduced and line influences are omitted
Extremely slim design
    Extremely slim casing of 6.2 mm combined with very low self heating allow tight mounting
Protective Separation acc. to EN 61140
    Protects service personnel and downstream devices against impermissibly high voltage
Maximum reliability
    No maintenance costs

Input Signal0(4) - 20 mA
Start-up Current< 200 mA
Voltage DropApprox. 2.3 V at 20 mA
Overload≤ 50 mA, 30 V
Output Signal0(4) - 20 mA
Load600 Ω
Response Time (T99)5 ms
Residual Ripple< 10 mVrms
Transmission Error< 0.1 % full scale
Load Error< 0.05 % of measured value / 100 Ω load
Temperature Coefficient< 100 ppm/K
Test Voltage3 kV AC, 50 Hz, 1 min. all circuits against one another
Working Voltage (Basic Insulation)600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1
Protection Against Electrical ShockProtective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient TemperatureOperation: -25 to + 70 °C (-13 to + 158 °F)
Transport and Storage: -40 to + 85 °C (-40 to + 185 °F)
EMCEN 61326-1
Construction62 x 96.5 x 107 mm , protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715
WeightApprox. 70 g
  • Thumbnail of document Data Sheet - IsoPAQ-611/612 1 & 2 Channel Loop Powered Isolators
    Download

    Data Sheet - IsoPAQ-611/612 1 & 2 Channel Loop Powered Isolators

    Download
  • Thumbnail of document Manual - IsoPAQ-611/612 1 & 2 Channel Loop Powered Isolators
    Download

    Manual - IsoPAQ-611/612 1 & 2 Channel Loop Powered Isolators

    Download
  • Thumbnail of document Data Sheet - IsoPAQ-611/612 1 & 2 Channel Loop Powered Isolators
    Download

    Data Sheet - IsoPAQ-611/612 1 & 2 Channel Loop Powered Isolators

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more