IsoPAQ-632 Isolation Signal Splitter/Repeater

Slim DIN rail 4-wire signal splitter/repeater w/ double outputs for mA & V signals

Buy now!
$527.00CAD
Have questions? We're here to help!
Have questions? We're here to help!

The Signal Splitter/Repeater IspPAQ-632 is used for isolation, conversion and distribution of 0/4 - 20 mA, 0/1 - 5 V and 0/2 - 10 V standard signals. The measuring input can also supply the loop power for 2-wire transmitters.

The input and two isolated outputs can be easily configured by using DIP switch. Due to the calibrated range selection no further adjustment is necessary.

The auxiliary power can be supplied via the connection terminals or via the optional In-Rail-Bus connector. A green LED on the front of the unit has been provided to monitor the power supply.

Calibrated signal setting via DIP switch
    Input and outputs can be set by using DIP switch – high precision without any further adjustment
4-Port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
Extremely slim design
    6.2 mm slim housing for a simple and space saving DIN rail mounting
Optional In-Rail-Bus mounting rail connector
    Allows for fast and economical installation
Protective Separation acc. to EN 61140
    Protects service personnel and downstream devices against impermissibly high voltage
Maximum reliability
    No maintenance costs

Input Signal (Calibrated Switchable)0 - 20 mA, 0 - 10 V, 0 - 5 V, 4 - 20 mA, 2 - 10 V, 1 - 5 V
Input ResistanceCurrent input: ≤ 35 Ω
Voltage input: ≥ 100 kΩ
OverloadCurrent input: < 50 mA
Voltage input: < 30 V
Transmitter Supply (Tx)16 V (open circuit voltage/short circuit current ≤ 22 V/35 mA)
Output Signal (Calibrated Switchable)0 - 20 mA, 0 - 10 V, 0 - 5 V, 4 - 20 mA, 2 - 10 V, 1 - 5 V
LoadCurrent output: ≤ 6 V (300 Ω at 20 mA)
Voltage output: ≤ 5 mA (2 kΩ at 10 V)
Linear Transmission Range–1 - +110 %
Residual Ripple< 10 mVrms
Transmission Error< 0.1 % full scale
Temperature Coefficient< 100 ppm/K
Cut-off Frequency (-3 dB)-3 dB 5 kHz
Response Time (T99)150 µs
Test Voltage3 kV AC, 50 Hz, 1 min.
Input against Output 1 against Output 2 against power supply
Working Voltage (Basic Insulation)600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1
Protection Against Electrical ShockProtective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient TemperatureOperation: -25 °C to + 70 °C (-13 to + 158 °F)
Transport and storage: -40 °C to + 85 °C (-40 to + 185 °F)
Power Supply24 V DC voltage range 16.8 - 31.2 V DC, approx. 1.4 W
EMCEN 61326-1
Construction62 x 96.5 x 107 mm , protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715
WeightApprox. 70 g
  • Thumbnail of document Data Sheet - IsoPAQ-632 Isolation Signal Splitter/Repeater
    Download

    Data Sheet - IsoPAQ-632 Isolation Signal Splitter/Repeater

    Download
  • Thumbnail of document Manual - IsoPAQ-632 Isolation Signal Splitter/Repeater
    Download

    Manual - IsoPAQ-632 Isolation Signal Splitter/Repeater

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more