Skip to main content
Press Enter
OMEGA

LVU501 Reflective Ultrasonic Level Transmitter

Reflective Ultrasonic Liquid Level Transmitter with Alarm Contacts (4) for Small Tanks

Have questions? We're here to help!
Have questions? We're here to help!

 The LVU500 Series general purpose reflective ultrasonic multi-function level transmitter provides continuous level measurement up to 3 m (9.8’) with a 4-20 mA analog signal output and four relays and is configured via web calibration software. The non-contact liquid level sensor features our proprietary Reflective Technology™ that delivers reliable level measurement in condensing environments. Each relay can be configured for alarm, automatic fill or empty functions. Select this sensor for small tanks with chemicals, water, wastewater and oil (non-foaming and/or highly vaporous liquids). Typical applications include day tank, IBC or drum, cooling tower, skid or machine, process tank and waste sumps.

• Offered in 1.5m (4.9’) and 3m (9.8’) measurement ranges 
• Fail-safe diagnostics with selectable relay and signal outputs 
• Narrow 2” (5cm) beam width for applications with limited space 
• Corrosion resistant PVDF transducer and compact PP enclosure 
• Short 1.5” (3.8cm) dead band maximizes tank filling capacity 
• Automatic temperature compensation from -40º to 80º C. 
RangeLVU501: 1.5” to 4.9' (3.8 cm to 1.5 m), LVU503: 4” to 9.8' (10.1 cm to 3 m)
AccuracyLVU501: 0.125” (3 mm), LVU503: ± 0.2% of range
ResolutionLVU501: 0.019” (0.5 mm), LVU503: 0.039” (1 mm)
DeadbandLVU501: 1.5” (3.8 cm), LVU503: 4” (10.1 cm)
Beam Width2” (5 cm)
ConfigurationWebCal® PC Windows® USB® 2.0
MemoryNon-volatile
Supply Voltage14-28 VDC
Max. Consumption0.5W
Loop resistance500 ohms @ 24 VDC
Signal Output4-20 mA, two-wire
Signal invert4-20 mA or 20-4 mA
Signal Fail-safe4 mA, 20 mA, 21 mA, 22 mA, hold last
Contact Type(4) SPST relays
Contact Rating60 VA, 1A maximum
Contact Fail-safeOpen, closed, hold last
Contact hystersisSelectable
Process tempF: -40 to 176º, C: -40 to 80º
Temp. comp.Automatic
Ambient temp.F: -31 to 140º, C: -35 to 60º
Pressure30 psi (2 bar)
Enclosure ratingType 6P (IP68)
Encl. materialPolypropylene
Transducer typeReflective Ultrasonic
Tranducer mat.Polyvinylidene fluoride
Cable jacket matPolyurethane
Cable type9-conductor, shielded
Cable length48” (1.2m)
Process mount2” NPT, or 2” G
Mount gasket2” G FKM®
ClassificationGeneral purpose
ApprovalUL 61010-1
ComplianceCE, RoHS
  • Thumbnail of document Data Sheet - LVU501 Reflective Ultrasonic Level Transmitter
    Download

    Data Sheet - LVU501 Reflective Ultrasonic Level Transmitter

    Download
  • Thumbnail of document Manual - LVU501 Reflective Ultrasonic Level Transmitter
    Download

    Manual - LVU501 Reflective Ultrasonic Level Transmitter

    Download

Request a Service Quote

Get a customized quote for calibration, validation, repair, or training services designed to keep your instruments accurate and compliant.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more