M12TX RTD Probe w/ 4 to 20mA Analog Output & M12 Connector
M12 Temperature Transmitter with 100Ω RTD
Supported Applications
The Omega M12TX series consists of analog PC-programmable 2-wire transmitters with integrated Pt100 RTD sensors. Designed for space-limited areas, these compact mineral-insulated probes feature a molded IP67 connector and are intended for industrial temperature measurement applications where the electronic section must remain within -40 to +80°C.
Operating Conditions & Performance
The M12TX series provides a configurable input temperature range from -50 to 800°C via software, with standard factory defaults typically set for ranges such as 0 to 150°C. The Pt100 sensor (Pt-0.00385) meets Class A accuracy in accordance with IEC751 up to 300°C. Transmitter accuracy is specified at a maximum of ±0.2°C or ±0.2% of span.
Performance characteristics include:
• Response Time (90%): <50 ms for the transmitter electronics.
• Sensor Response Time (63.2%, test in water to IEC751): Less than 3.5 seconds for Ø3 mm probes and less than 13 seconds for Ø6 mm probes.
• Ambient Temperature: -40 to +80°C (for the electronic section).
• Process Temperature Limits: Up to 500°C (-58 to 932°F) is listed for standard operation; higher process temperatures up to 800°C are configurable but require adherence to Tmax./Tenv. graphs to prevent damage from heat transfer.
• Humidity: 0 to 100% relative humidity.
Configuration Options
The series supports a wide envelope of configurations for probe diameter, insertion length, and output parameters. The transmitter is powered by an external supply or via the configuration interface during setup.
• Sensor Element: 3-wire Pt100 (Pt-0.00385) with a sensor current of 0.5 mA; maximum wire resistance per wire is 20 Ω.
• Output Signal: 4 to 20 mA analog output, non-isolated. Permissible load is 700Ω @24Vdc (calculated as R_load = (U - 8.5) / 0.022).
• Power Supply: 8.5 to 32 Vdc with polarity protection.
• Housing & Materials: Thermoplastic body for the transmitter section; probe sheath and thermowell options include AISI 316L stainless steel or compact mineral-insulated (MgO) cable construction.
• Degree of Protection: IP65 and IP67 in accordance with IEC60529. The molded connector is M12x1 male, compliant with VDE0627.
• Error Monitoring: Configurable sensor break monitoring (upscale >21 mA or downscale <3.6 mA) and fixed short-circuit action (downscale <3.6 mA).
Key Product Differences
Variants within the M12TX series are distinguished by probe diameter, insertion length, and specific model families.
• Diameter Options: Probes are available in 3 mm (approx. 1/8") or 6 mm (approx. 1/4").
• Length Configurations: Insertion lengths range from 100 mm to 1000 mm, with specific inch-based variants including 4", 6", 9", 12", 18", and 24".
• Bending Radius: The compact mineral-insulated cable probe allows a minimum bending radius of three times the outer diameter (excluding the sensing tip).
• Configuration Kit: Programming is performed using the M12TX-CONFIG-SET, which includes USB interface hardware and software for Windows 10.0 or higher to adjust range span, units (°C/°F/K), sensor error compensation, and transmitter identification.
• Programmable Transmitter
• Molded Connector (IP67)
• M12 Connection
• 4 to 20 mA Output
| Accuracy | Class A |
| Body Material | Thermoplastic |
| Downscale | 3.6 mA |
| Electrical Output | 4 to 20 mA |
| EMC | In accordance to EN 61326 |
| Enclosure Ratings | IP67 |
| Enclosure Ratings Note | IP65 and IP67 in accordance to IEC60529 |
| Factory Setting | 0 to 150°C/sensor break >21 mA (upscale) |
| Operating Temperature, Max | 80 °C |
| Operating Temperature, Min | -40 °C |
| Permissible Load | 700 |
| Permissible Load Note | 700 @ 24 Vdc [RLo= (Vsupply-8.5)/0.020] |
| Process Connection Size | N/A |
| Process Temperature, Max | 500 °C |
| Process Temperature, Min | -50 °C |
| Range Configurations Note | It is possible set the input temperature range (span) by the M12TX-CONFIG-SETconfiguration kit (PC with OS Windows® required) |
| Relative Humidity, Max | 1 |
| Relative Humidity, Min | 0% |
| Response Time | < 50 ms |
| RTD Type | 100 Ω Pt Sensor |
| Sensor Break Monitoring Note | Selectable: Upscale (>21.0 mA) or downscale (<3.6 mA) action Sensor Short-Circuit: Fixed to downscale (<3.6 mA) action |
| Sensor Error Compensation Note | Over 2 points (maximum 1% of span) |
| Series ID | M12TX |
| Span, Min | 50°C |
| Span Note | 50°C (122°F) [if the zero value is set between one of these values: -40°C (-40°F), -20°C (-4°F), 0°C (32°F), 20°C (68°F), 40°C (104°F), the minimum span is 20°C (68°F) rather than 50°C (122°F)] |
| Supply Power Effects | Negligible |
| Supply Voltage | 8.5 to 32 Vdc |
| Temperature Influence, Max | ± 0.3% |
| Temperature Influence Note | Maximum of ± 0.3°C/25°C (77°F) or ± 0.3% of span/25°C (77°F) |
| Temperature Sensor Type | RTD |
| Thermocouple Type | N/A |
| Tmax. Electronic | 80°C |
| Upscale | 21 mA |