Supported Applications
The Omega M12TXSS series consists of stainless steel RTD temperature transmitters designed for compact installations where space is limited. These devices integrate a Pt100 sensor with an analog transmitter to provide direct process monitoring in industrial environments requiring secure, threaded mounting.
• Temperature measurement and signal conditioning via 4 to 20 mA output
• Applications utilizing M12 male connector interfaces for electrical connection
Operating Conditions & Performance
The series is engineered for a process temperature range of -50 to +120°C (-58 to 248°F). The electronic section operates within an ambient temperature range of -40 to +80°C. Accuracy specifications include Class A sensor performance in accordance with IEC751 and a transmitter accuracy maximum of ±0.2°C or ±0.2% of span.
• Response time: <3.5 seconds for the 3 mm diameter probe (tested in water to IEC751, reaching 63.2% of thermal gap)
• Enclosure rating: IP65 and IP67 in accordance with IEC60529
• Humidity tolerance: 0 to 100% relative humidity
Configuration Options
The M12TXSS series offers configurable parameters via the M12TX-CONFIG-SET kit, which includes a USB interface and software for Windows®. The transmitter supports input temperature range configuration between -50°C to 800°C (span), sensor break monitoring selection (upscale or downscale action), and measurement unit settings.
• Probe lengths: 13 mm (0.51") or 24 mm (0.94"); diameter is fixed at 3 mm (0.1")
• Housing material: Stainless steel AISI 316L with a thermowell construction
• Process connections: Standard 1/8" NPT male thread or G1/8 metric thread options
• Electrical output: 4 to 20 mA signal; permissible load is 700Ω @ 24 Vdc (calculated as R_load = (U - 8.5) / 0.022)
• Power supply: 8.5 + 32 Vdc with polarity protection
Key Product Differences
The series is distinguished by probe insertion length and thread standard, resulting in specific model configurations:
• M12TXSS-PT100-13MM variants: 13 mm (0.51") long with either 1/8" NPT or G1/8 threads
• M12TXSS-PT100-24MM variants: 24 mm (0.94") long with either 1/8" NPT or G1/8 threads
Factory default parameters are set to a range of 0+150°C for most models, though the M12TXSS series defaults to 0+100°C (32 to 212°F) with upscale sensor break indication (>21 mA). The device is non-isolated and features an M12 male connector output.
| Accuracy | Class A |
| Accuracy Detail | Class A per IEC60751 |
| Body Material | Stainless Steel AISI 316L |
| Downscale | 3.6 mA |
| Electrical Output | 4 to 20 mA |
| EMC | In accordance to EN 61326 |
| Enclosure Ratings | IP67 |
| Enclosure Ratings Note | IP65 and IP67 in accordance to IEC60529 |
| Factory Setting | 0 to 100°C/ sensor break >21 mA (upscale) |
| Operating Temperature, Max | 80 °C |
| Operating Temperature, Min | -40 °C |
| Permissible Load | 700 |
| Permissible Load Note | 700 @ 24 Vdc [RLo= (Vsupply-8.5)/0.020] |
| Probe Diameter | 3 mm |
| Process Temperature, Max | 120 °C |
| Process Temperature, Min | -50 °C |
| Range Configurations Note | It is possible set the input temperature range (span) by the M12TX-CONFIG-SETconfiguration kit (PC with OS Windows® required) |
| Relative Humidity, Max | 1 |
| Relative Humidity, Min | 0% |
| Response Time | < 50 ms |
| Response Time Note | Diameter 3 mm (0.12") <3.5 seconds, diameter 6 mm (0.24") <13 seconds (test in water to IEC751- time for reaching 63.2% of instantaneous temperature change) |
| RTD Type | 100 Ω Pt Sensor |
| Sensor Break Monitoring Note | Selectable: Upscale (>21.0 mA) or downscale (<3.6 mA) action Sensor Short-Circuit: Fixed to downscale (<3.6 mA) action |
| Sensor Error Compensation Note | Over 2 points (maximum 1% of span) |
| Series ID | M12TXSS |
| Span, Min | 50°C |
| Span Note | 50°C (122°F) [if the zero value is set between one of these values: -40°C (-40°F), -20°C (-4°F), 0°C (32°F), 20°C (68°F), 40°C (104°F), the minimum span is 20°C (68°F) rather than 50°C (122°F)] |
| Supply Power Effects | Negligible |
| Supply Voltage | 8.5 to 32 Vdc |
| Temperature Influence, Max | ± 0.3% |
| Temperature Influence Note | Maximum of ± 0.3°C/25°C (77°F) or ± 0.3% of span/25°C (77°F) |
| Temperature Sensor Type | RTD |
| Thermocouple Type | N/A |
| Tmax. Electronic | 80°C |
| Upscale | 21 mA |
| Zero Setting Adjustable Range | Any value between -50 to 50°C (-58 to 122°F) |