Skip to main content
Press Enter
OMEGA

OME-DB-8225/1 100 S/s 16-Channel 16-Bit Analog Input Board for the ISA Bus

100 S/s 16-Channel 16-Bit Analog Input Board for the ISA Bus

Normally ships in
2-3 weeks
Have questions? We're here to help!
Have questions? We're here to help!
Configure

Supported Applications

The Omega OME-A-826PG series is a multifunction interface card designed for data acquisition applications. It provides analog-to-digital (A/D), digital-to-analog (D/A), and digital I/O capabilities within an ISA-Bus architecture. The product overview identifies support for software development in VC++, VB, Delphi, and Borland C++ Builder environments.

Operating Conditions & Performance

The series delivers 16-bit resolution A/D conversion across 16 channels configured as single-ended or 8 channels in differential mode. D/A output is provided on 2 channels with 12-bit resolution, configurable for a 0-5V or 0-10V range via hardware JP1 setting. Digital I/O consists of 16 TTL-compatible digital input channels and 16 TTL-compatible digital output channels.

Software Support

• Windows 95/98: Supported by A826.dll, A826.lib libraries, and the A826.Vxd device driver.
• Windows NT: Supported by A826.dll, A826.lib libraries, and the A826.sys/Napwnt.sys device drivers.

The series documentation notes that these products are not designed for use in patient-connected applications. Omega Engineering holds ISO 9001 certification (Stamford, CT) and ISO 9002 certification (Manchester, UK).

Signal Configuration

• A/D Input: Low gain settings of 1/2/4/8 are available; analog input signal range configuration codes are detailed in Section 4.1 of the source manual.
• D/A Output: Voltage ranges (0-5V or 0-10V) are selected by hardware JP1 setting.

Configuration Options

The series is available as an ISA-Bus interface card. The documented capabilities include the following configurable parameters:

• Analog Input Channels: 16 single-ended or 8 differential.
• Digital I/O: 16 TTL-compatible inputs and 16 TTL-compatible outputs.
• Resolution: 16-bit A/D, 12-bit D/A.

The series supports integration with Windows-based development environments through provided subroutines (A826.DLL and A826.Vxd).

Key Product Differences

The OME-A-826PG-series is identified as a 100 sample per second, 16-channel analog input board for the ISA Bus. The series includes variants such as OME-DB-8225/1 and OME-DB-8225/2 within the optional boards family.

Documentation distinguishes between driver files required for different operating systems: A826.Vxd is specified for Windows 95/98, while A826.sys and Napwnt.sys are listed for Windows NT. The series title references a sampling rate of 100 samples per second.

• 16-Bit A/D Converter
• 12-Bit D/A Converter
• 16 Single-Ended or 8 Differential Inputs
• 100 KS/s Sampling Rate
ADC Resolution16 bit
Additional Features 11 m 37-pin D-sub Cable
ChannelsInterrupt Channel: 3-15 jumper selectable"
Conversion Rate100 KS/s
Counter Input NoteCounter Timer Type: 82C54,A/D Pacer: 16-bit counter
Digital I/O NoteInputs: 16 (LSTTL) Input Low: VIL = 0.8 V max IIL = -0.4 mA max Input High: VIH = 2.0 V min IIH = 20 µA max Outputs: 16 channel TTL levels Outputs Low: VOL = 0.5 V max @ IOL = 8 mA max Outputs High: VOH = 2.7 V min IOH = -400 µA max
Electrical ConnectionAnalog I/O, 37-pin D-Sub; digital I/O, two 20-pin headers
Height122 mm
Impedance Input10,000 Ω/6pf
Linearity+1-bit
Number of Channels1,2
Number of Channels Note16-channel single-ended or 8-channel differential; Channels: 2 independent;Type: 12-bit double buffers;Linearity: 0.006% FS;Output Driving: 5 mA;Output Range: 0 to 5 V or 0 to 10 V;External Reference: Max +10 V;Output Current: +5 mA
Operating Temperature, Max50 °C
Operating Temperature, Min0 °C
Over-Voltage Protection+35 V
Power Consumption+5 V @ 650 mA
Relative Humidity0 to 90 % RH non-condensing
Samples NoteSample-and-Hold: On-Chip
Series IDOME-A-826PG-series
SoftwareWindows 95/98/NT
Storage Temperature, Max70 °C
Storage Temperature, Min-20 °C
Timer Measurement Range0.0045 Hz
Voltage Measurement Range+10 V, +5 V, +2.5 V, +1.25 V
Width170 mm
Zero Drift19 ppm/°C of full scale
  • Download

    Manual - OME-DB-8225/1 100 S/s 16-Channel 16-Bit Analog Input Board for the ISA Bus

    Download

Request a Calibration Quote

We’re here to make calibration easy. Request a quote today and let our team give you the care, precision, and service you can trust.
Learn more

Browse By Brands

Uncover the brands that set the standard for quality and dependability in every industry we serve.
Learn more